background image

6 Installation

Installer reference guide

15

35R5V1B RXM20~35R5V1B
R32 Split Series
4P519439-8H – 2020.07

▪ When  it  is  expected  that  the  operating  pressure  will  be  low  (e.g.

when  cooling  will  be  performed  while  the  outside  air  temperature
is  low),  sufficiently  seal  the  flare  nut  in  the  stop  valve  on  the  gas
line with silicon sealant to prevent freezing.

Silicon sealant, make sure there is no gap.

To open/close the stop valve

1

Remove the stop valve cover.

2

Insert  a  hexagon  wrench  (liquid  side:  4  mm,  gas  side:  6  mm)
into the valve stem and turn the valve stem:

Counterclockwise to open
Clockwise to close

3

When  the  stop  valve  CANNOT  be  turned  any  further,  stop
turning.

4

Install the stop valve cover.

Result: 

The valve is now open/closed.

To handle the stem cap

▪ The  stem  cap  is  sealed  where  indicated  with  the  arrow.  Do  NOT

damage it.

▪ After handling the stop valve, tighten the stem cap, and check for

refrigerant leaks.

Item

Tightening torque (N∙m)

Stem cap, liquid side

14.2~17.2

Stem cap, gas side

17.1~20.9

To handle the service cap

▪ ALWAYS use a charge hose equipped with a valve depressor pin,

since the service port is a Schrader type valve.

▪ After  handling  the  service  port,  tighten  the  service  port  cap,  and

check for refrigerant leaks.

Item

Tightening torque (N∙m)

Service port cap

10.8~14.7

6.4.7

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

6.5

Checking the refrigerant piping

6.5.1

About checking the refrigerant piping

The outdoor unit's 

internal

 refrigerant piping has been factory tested

for  leaks.  You  only  have  to  check  the  outdoor  unit's 

external

refrigerant piping.

Before checking the refrigerant piping

Make  sure  the  refrigerant  piping  is  connected  between  the  outdoor
unit and the indoor unit.

Typical workflow

Checking  the  refrigerant  piping  typically  consists  of  the  following
stages:

1

Checking for leaks in the refrigerant piping.

2

Performing  vacuum  drying  to  remove  all  moisture,  air  or
nitrogen from the refrigerant piping.

If  there  is  a  possibility  of  moisture  being  present  in  the  refrigerant
piping  (for  example,  water  may  have  entered  the  piping),  first  carry
out  the  vacuum  drying  procedure  below  until  all  moisture  has  been
removed.

6.5.2

Precautions when checking the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

NOTICE

Use  a  2-stage  vacuum  pump  with  a  non-return  valve  that
can  evacuate  to  a  gauge  pressure  of  −⁠100.7  kPa
(−⁠1.007  bar)(5  Torr  absolute).  Make  sure  the  pump  oil
does not flow oppositely into the system while the pump is
not working.

NOTICE

Use  this  vacuum  pump  for  R32  exclusively.  Using  the
same  pump  for  other  refrigerants  may  damage  the  pump
and the unit.

NOTICE

▪ Connect  the  vacuum  pump  to  the  service  port  of  the

gas stop valve.

▪ Make sure that the gas stop valve and liquid stop valve

are  firmly  closed  before  performing  the  leak  test  or
vacuum drying.

Summary of Contents for RXM20R5V1B

Page 1: ...Installer reference guide R32 Split Series English Installer reference guide R32 Split Series RXM20R5V1B RXM25R5V1B RXM35R5V1B ARXM25R5V1B ARXM35R5V1B...

Page 2: ...15 6 5 3 To check for leaks 16 6 5 4 To perform vacuum drying 16 6 6 Charging refrigerant 16 6 6 1 About charging refrigerant 16 6 6 2 About the refrigerant 17 6 6 3 Precautions when charging refriger...

Page 3: ...er operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Improper i...

Page 4: ...ed in the duct work air inlet AND outlet are connected directly to the same room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet NOTICE Precautions shall be...

Page 5: ...7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg Amin m2 4 6 20 0 4 8 21 8 5 0 23 6 1 842 5 2 25 6 1 843 4 45 5 4 27 6 2 0 4 83 5 6 29 7 2 2 5 31 5 8 31 8 2 4 5 79 6 0 34 0 2 6 6 39...

Page 6: ...form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately If the valve is NOT closed immediately rem...

Page 7: ...lers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the...

Page 8: ...he accessories at the bottom of the package 1 1 1 1 1 1 b e c d a f a General safety precautions b Outdoor unit installation manual c Fluorinated greenhouse gases label d Multilingual fluorinated gree...

Page 9: ...NING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and ob...

Page 10: ...winds Example Behind the building b c a If the outdoor unit is exposed to direct sea winds install a windbreaker Height of windbreaker 1 5 height of outdoor unit Mind the service space requirements wh...

Page 11: ...e equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fus...

Page 12: ...se a vibration proof rubber field supply in cases where vibrations may be transmitted to the building Fix the unit securely by means of foundation bolts in accordance with the foundation drawing Prepa...

Page 13: ...when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation DANGER RISK OF BURNING SCALDING CAUTION...

Page 14: ...t refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut...

Page 15: ...ervice port 2 Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit...

Page 16: ...ying again NOTICE Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor INFORMA...

Page 17: ...To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the factory refrigerant charge see unit name plate the determined additional a...

Page 18: ...o NOT branch the power supply for the drain pump etc from the terminal block This could result in electrical shock or fire WARNING Keep the interconnection wiring away from copper pipes without therma...

Page 19: ...ck or leakage 3 Open the wire clamp 4 Connect the interconnection cable and power supply as follows 50 Hz 220 240 V c d f a b e a Interconnection cable b Power supply cable c Circuit breaker d Earth l...

Page 20: ...be closed Power up the unit after it is closed The indoor unit is properly mounted The outdoor unit is properly mounted The system is properly earthed and the earth terminals are tightened The power s...

Page 21: ...t least once a year However applicable legislation might require shorter maintenance intervals NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the...

Page 22: ...e connection of the earth wiring 11 3 5 Symptom Unit does NOT function or burn damage Possible causes Corrective action The wiring was NOT performed in accordance with the specifications Correct the w...

Page 23: ...orced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 12 3 To start and stop forced cooling There are 2 methods to perform forced cooling Me...

Page 24: ...TCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GR...

Page 25: ...r application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructio...

Page 26: ......

Page 27: ......

Page 28: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 4P519439 8H 2020 07 Copyright 20...

Reviews: