Wiring

 WARNING

1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leakage breaker capable handling harmonics in order 
to prevent malfunctioning of the earth leakage breaker itself.)

4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm). 

2) Connect the inter-unit wirings between the 

indoor and outdoor units 

so that the terminal 

numbers match.

 Tighten the terminal screws 

securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal 
board.

Observe the notes mentioned below when wiring to the power supply terminal board.
Precautions to be taken for power supply wiring. 
Use a round crimp-style terminal for connection to the power supply  terminal board. 
In case it cannot be used due to unavoidable reasons, be sure to observe the follow-
ing instruction.
Place the round crimp-style terminals on the wires up to the covered part and 
secure in place.

 CAUTION

When connecting the inter-unit wirings to the terminal board using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

1
2
3

1 2 3

L N

Safety 
breaker 
10A

Earth leakage 
circuit breaker

Earth

When wire length exceeds 10m, 
use 2.0mm diameter wires.

H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Use 2.0mm diameter wires.

1

2

3

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

Power supply
terminal block

1

2

3

Shape wires so 
that the stop valve 
cover fit securely.

Stranded Wire

Round crimp-style
terminal

Strip wire end
to this point.

Excessive strip length
may cause electrical
shock or leakage.

Good

Wrong

Stripping wire at terminal block

01_EN_3P232550-1.fm  Page 10  Saturday, August 30, 2008  5:57 PM

Summary of Contents for RXL20G2V1B

Page 1: ...LATION MANUAL Installation manual Installationsmanual Installationshandbok Installasjonsh ndbok Asennusohje Installierungshandbuch Manuel d installation Instrukcja montazu Installatiehandleiding R410A...

Page 2: ...RXL20G2V1B DAIKIN INDUSTRIES LTD Noboru Murata Manager Quality Control Department 1st of Sep 2008 Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC DAIKIN TCF 015 M3 07 2008 KEMA Qualit...

Page 3: ...control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant c...

Page 4: ...hey are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since...

Page 5: ...or unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Additional refrigerant required for refrigerant...

Page 6: ...ans of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their length are 2...

Page 7: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 8: ...top valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping...

Page 9: ...mal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Thickness 10mm Min 30mm or more Thickness 0 8mm C1220T O Filling a cylinder with an attached siphon Stand the cylinder upr...

Page 10: ...er supply is turned OFF Turn it OFF if has not been turned OFF 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn ON the main power supply CAUTION...

Page 11: ...prox 15 minutes CAUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve close the gas stop v...

Page 12: ...cautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoidable reasons be sure to observe...

Page 13: ...wer in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut of...

Page 14: ...0809 HT 3P232550 1 M08B046 Two dimensional bar code is a code for manufacturing 00_CV_3P232550 1 fm Page 2 Tuesday August 12 2008 9 29 PM...

Reviews: