Installation Space Requirements

•  Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation space 

requirements below.

• 

For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

More than 

1-15/16 (50)

More than 

1-15/16 (50)

More than 

5-7/8 (150)

More than 

3-15/16 (100)

More than 

1-15/16 (50)

More than 

3-15/16 (100)

Side view

47-1/4

(1200)

or less

Wall facing one side

Walls facing two sides

Top view

Top view

More than 5-7/8 (150)

More than 

11-13/16 (300)

More than 

1-15/16 (50)

Walls facing three sides

 unit: inch (mm)    

 unit: inch (mm)    

Top view

More than 3-15/16 (100)

More than 

13-3/4 (350)

More than 

1-15/16 (50)

Walls facing three sides

More than 

3-15/16 (100)

More than

13-3/4 (350)

Side view

47-1/4

(1200)

or less

Wall facing one side

More than 

1-15/16 (50)

More than 

1-15/16 (50)

Top view

More than 

3-15/16 (100)

Walls facing two sides

More than 

13-3/4 (350)

09/12 class

15/18/24 class

Outdoor Unit Installation

1. 

Installing the outdoor unit

1) When installing the outdoor unit, refer to “

Precautions for Selecting a Location

” and the “

Outdoor Unit Installation Diagram

”.

2) If drain work is necessary, follow the procedures on the next page.

01_EN_3P379970-10C.indd   5

10/18/2019   9:17:59 AM

Summary of Contents for RXL15QMVJUA

Page 1: ...lish Fran ais Espa ol DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n MODELS RXL15QMVJU RXL15QMVJUA Manuel dinstallati...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 10C M19B229 1912 HT...

Reviews: