background image

3 About the box

Installation manual

6

RXJ42+50A

R32 split series

3P512025-12X – 2021.12

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing indoor unit installation (see 

"8 Finishing the outdoor

unit installation"

 [

4

 12])

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn OFF the power supply before servicing.

▪ Install  the  switch  box  cover  before  turning  ON  the

power supply.

Configuration (see 

"9 Configuration"

 [

4

 12])

WARNING

Before  connecting  or  disconnecting  the  connector,  make
sure the power supply is turned OFF.

Commissioning (see 

"10 Commissioning"

 [

4

 12])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

Maintenance and service (see 

"11 Maintenance and

service"

 [

4

 13])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel, remove the fuses or open the protection devices
of the unit.

▪ Do NOT touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

▪ Please  note  that  some  sections  of  the  electric

component box are hot.

▪ Make sure you do NOT touch a conductive section.

▪ Do NOT rinse the unit. This may cause electric shocks

or fire.

About the compressor

DANGER: RISK OF ELECTROCUTION

▪ Use this compressor on a grounded system only.

▪ Turn the power off before servicing the compressor.

▪ Reattach  the  switch  box  cover  and  service  lid  after

servicing.

CAUTION

ALWAYS wear safety glasses and protective gloves.

DANGER: RISK OF EXPLOSION

▪ Use a pipe cutter to remove the compressor.

▪ Do NOT use the brazing torch.

▪ Use approved refrigerants and lubricants only.

DANGER: RISK OF BURNING/SCALDING

Do NOT touch the compressor with bare hands.

3

About the box

3.1

Outdoor unit

3.1.1

To remove the accessories from the
outdoor unit

1

Lift the outdoor unit.

2

Remove the accessories at the bottom of the package.

b

e

c

d

a

f

g

h

a

General safety precautions

b

Outdoor unit installation manual

c

Fluorinated greenhouse gases label

d

Multilingual fluorinated greenhouse gases label

e

Drain plug (located on the bottom of the packing case)

f

Drain cap (1)

g

Drain cap (2)

h

Energy label

4

Unit installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

Summary of Contents for RXJ42A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXJ42A2V1B RXJ50A2V1B...

Page 2: ...sina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele resp...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...14 14 2 Piping diagram 15 14 2 1 Piping diagram Outdoor unit 15 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to k...

Page 5: ...the formation of a harmful gas Turn OFF any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the unit until a service person confirms that...

Page 6: ...is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING WARNING Before carrying out any m...

Page 7: ...igned for outdoor installation only and for ambient temperatures specified in the table below unless otherwise specified in the operation manual of the connected indoor unit Cooling Heating 10 50 C DB...

Page 8: ...asures so that the evacuated condensate CANNOT freeze 1 Install drain caps 1 and 2 accessory Make sure the edges of the drain caps close off the holes completely a b a Bottom frame b Drain cap 2 Insta...

Page 9: ...2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage WARNING Connect the r...

Page 10: ...er than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the...

Page 11: ...y the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire...

Page 12: ...t the facility mode When cutting jumper J6 on the PCB the operation range will expand to 15 C The facility mode will stop if the outdoor temperature drops below 20 C and resume when the temperature ri...

Page 13: ...e temperature In heating mode select the highest programmable temperature Test run can be disabled if necessary 2 When the test run is finished set the temperature to a normal level In cooling mode 26...

Page 14: ...circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown...

Page 15: ...solenoid valve coil Z C Ferrite core ZF Z F Noise filter 14 2 Piping diagram 14 2 1 Piping diagram Outdoor unit PED categories of equipment High pressure switch category IV Compressor category II Othe...

Page 16: ...3P512025 12X 2021 12 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: