4 Unit installation

Installation manual

7

RXJ42+50A
R32 split series
3P512025-12X – 2021.12

4.1

Preparing the installation site

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

4.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

>100

>50

>350

(mm)

b

a

>100

>50

b

a

>100

b

a

b

a

>350

>350

>50

b

a

a

Air outlet

b

Air inlet

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

The  outdoor  unit  is  designed  for  outdoor  installation  only  and  for
ambient temperatures specified in the table below (unless otherwise
specified in the operation manual of the connected indoor unit).

Cooling

Heating

–10~50°C DB

–20~24°C DB

4.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

It  is  recommended  to  provide  at  least  150  mm  of  free  space  below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See 

"4.2 Mounting

the outdoor unit"

 [

4

 7] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

Summary of Contents for RXJ42A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXJ42A2V1B RXJ50A2V1B...

Page 2: ...sina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele resp...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...14 14 2 Piping diagram 15 14 2 1 Piping diagram Outdoor unit 15 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to k...

Page 5: ...the formation of a harmful gas Turn OFF any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the unit until a service person confirms that...

Page 6: ...is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING WARNING Before carrying out any m...

Page 7: ...igned for outdoor installation only and for ambient temperatures specified in the table below unless otherwise specified in the operation manual of the connected indoor unit Cooling Heating 10 50 C DB...

Page 8: ...asures so that the evacuated condensate CANNOT freeze 1 Install drain caps 1 and 2 accessory Make sure the edges of the drain caps close off the holes completely a b a Bottom frame b Drain cap 2 Insta...

Page 9: ...2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage WARNING Connect the r...

Page 10: ...er than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the...

Page 11: ...y the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire...

Page 12: ...t the facility mode When cutting jumper J6 on the PCB the operation range will expand to 15 C The facility mode will stop if the outdoor temperature drops below 20 C and resume when the temperature ri...

Page 13: ...e temperature In heating mode select the highest programmable temperature Test run can be disabled if necessary 2 When the test run is finished set the temperature to a normal level In cooling mode 26...

Page 14: ...circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown...

Page 15: ...solenoid valve coil Z C Ferrite core ZF Z F Noise filter 14 2 Piping diagram 14 2 1 Piping diagram Outdoor unit PED categories of equipment High pressure switch category IV Compressor category II Othe...

Page 16: ...3P512025 12X 2021 12 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: