Trial Operation and Testing

1.

Trial operation and testing

1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable 

temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26°C to 28°C in cooling mode, 20°C to 24°C 

in heating mode).

3) For protection, the system disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts, 

such as louver movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

2.

Test items 

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet has clear path of air.
Stop valves are opened.

Incomplete cooling/heating 
function

Indoor unit properly receives remote control commands.

Inoperative

3PEN358184-1E.book  Page 12  Friday, November 13, 2015  12:54 PM

Summary of Contents for RXG20L2V1B

Page 1: ...rlands Manual de instalación Serie Split R410A Español Manuale d installazione Serie Multiambienti R410A Italiano Εγχειρίδιο εγκατάστασης ιαιρούμενης σειράς R410A Ελληνικά Manual de Instalação Série split R410A Portugues Руководство по монтажу Серия R410A с раздельной установкой Русский Montaj kılavuzları R410A Split serisi Türkçe Models RXG20L2V1B RXG25L2V1B RXG35L2V1B 3PEN358184 1E book Page 1 F...

Page 2: ......

Page 3: ...te da B secondo il Certificato C 07 ȈȘȝİȓȦıȘ ȩʌȦȢ țĮșȠȡȓȗİIJĮȚ ıIJȠ A țĮȚ țȡȓȞİIJĮȚ șİIJȚțȐ Įʌȩ IJȠ B ıȪȝijȦȞĮ ȝİ IJȠ ȆȚıIJȠʌȠȚȘIJȚțȩ C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 ɉɪɢɦɟɱɚɧɢɟ ɤɚɤ ɭɤɚɡɚɧɨ ɜ A ɢ ɜ ɫɨɨɬɜɟɬɫɬɜɢɢ ɫ ɩɨɥɨɠɢɬɟɥɶɧɵɦ ɪɟɲɟɧɢɟɦ B ɫɨɝɥɚɫɧɨ ɋɜɢɞɟɬɟɥɶɫɬɜɭ C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 1...

Page 4: ...hen wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into ...

Page 5: ...ing or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle p...

Page 6: ...to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit Tighten the screws Stop valve cover Allow space for piping and electrical servicing Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfo...

Page 7: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of at least 30mm in height under th...

Page 8: ...g the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A A Cut exactly at right angles Remove burrs Set exactly at the position shown below Flaring Die Check Flare s inner surface must be flaw free The pipe end must be evenly flared in a perfect circle Mak...

Page 9: ...ich comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few...

Page 10: ... piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Thickness 10mm Min 30mm or more Thickness 0 8mm C1220T O Filling a cylinder with an attached siphon Stand the cylinder upright when ...

Page 11: ...rn it off if it has not been turned off 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electricity saving make sure that the main power supply is turned off The selective connector for standby electricity saving is required if an indoor u...

Page 12: ...emp or Temp button 4 Press the Mode button to start the trial operation 5 Press the Mode button and select operation mode 6 Trial operation terminates in approx 30 minutes and switches into normal mode To quit trial operation press the On Off button Using the outdoor unit forced cooling operation switch with standby electricity saving function turned off Push on SW1 with a screwdriver The operatio...

Page 13: ... below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires If the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal bloc...

Page 14: ...ser DISCHARGE Discharge C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 Fuse FU4 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fan motor MRCW MRM10 MRM20 MR30 Magnetic relay N Neutral Q1L Overload protector Q1DI Earth leak detector PCB1 PCB2 Printed circuit board S10 S11 S12 S20 S40 S70 S80 S90 HL3 HN3 X11A Connector R1T R2T R3T Thermistor SA1 Surge abs...

Page 15: ...unt of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and outdoor units ...

Page 16: ...3P358184 1E 2015 10 Copyright 2014 Daikin 3PEN358184 1E book Page 1 Friday November 13 2015 12 54 PM ...

Reviews: