background image

3

6

• Split Sky Air • Outdoor Units

11

• Outdoor Units • R-410A • RXG-E2V1B

6

Piping diagram

3D045139D

RXG25-35E

Outdoor temperature thermistor

Heat exchanger

Propeller fan

Liquid stop valve

Field piping

Field piping

Accumulator

Compressor

Muffler

Refrigerant flow

Cooling

Heating

Discharge pipe

thermistor

Heat exchanger thermistor

Muffler with

filter

Muffler

Motor operated valve

Four way valve
on : heating

Outdoor unit

Gas stop valve

Muffler with

filter

Filter

Summary of Contents for RXG-E2V1B

Page 1: ...technical data RXG E2V1B Outdoor Units Pair Application air conditioning systems Split Sky Air...

Page 2: ...nal Input 3 Technical Specifications 3 Electrical Specifications 4 3 Electrical data 5 4 Capacity tables 7 Cooling Heating capacity tables 7 5 Dimensional drawing centre of gravity 9 Dimensional drawi...

Page 3: ...t S k y R X G E 2 V 1 B R 4 1 0 A Outdoor units for pair application Outdoor units are fitted with a swing compressor renowned for its low noise and high energy efficiency Daikin outdoor units are ne...

Page 4: ...0 3 8 Heating Minimum kW 1 3 1 4 Standard kW 3 4 4 2 Maximum kW 4 5 5 0 For combination indoor units outdoor units EER Cooling 4 03 3 30 COP Heating 4 15 3 72 Energy Labeling Directive Cooling A Heat...

Page 5: ...plug Quantity 1 1 Notes Nominal cooling capacities are based on indoor temperature 27 CDB 19 CWB outdoor temperature 35 CDB equivalent refrigerant piping 7 5m level difference 0m Nominal heating capa...

Page 6: ...22 0 50 50 240 3 1 0 21 0 48 3D045220B SYMBOLS MCA Min Circuit Amps A MFA Max Fuse Amps A RLA Rated Load Amps A OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps A W Fan Motor Rated Outpu...

Page 7: ...0 22 0 50 50 240 4 5 0 21 0 48 3D045221B SYMBOLS MCA Min Circuit Amps A MFA Max Fuse Amps A RLA Rated Load Amps A OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps A W Fan Motor Rated Outp...

Page 8: ...7 3 49 0 81 3 80 0 84 18 0 2 22 0 71 2 60 0 74 2 99 0 78 3 45 0 82 3 75 0 84 20 0 2 17 0 72 2 56 0 75 2 94 0 78 3 40 0 83 3 71 0 85 21 0 2 15 0 72 2 53 0 75 2 92 0 79 3 38 0 83 3 68 0 86 22 0 2 12 0 7...

Page 9: ...TC PI TC PI 16 0 2 80 0 96 3 27 1 01 3 75 1 06 4 32 1 11 4 70 1 15 18 0 2 74 0 98 3 21 1 02 3 69 1 07 4 26 1 12 4 64 1 16 20 0 2 68 0 99 3 16 1 03 3 63 1 08 4 20 1 14 4 57 1 17 21 0 2 65 0 99 3 13 1...

Page 10: ...mum space for air passage Wall height on air outlet side less than 1200 Drain outlet I D J 15 9 hose for connection 4 x holes for anchor bolts M8 or M10 Name plate Terminal strip with earth terminal W...

Page 11: ...Outdoor Units R 410A RXG E2V1B 5 Split Sky Air Outdoor Units 10 5 Dimensional drawing centre of gravity 5 2 Centre of gravity RXG25 35E 4D044107F...

Page 12: ...rmistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Accumulator Compressor Muffler Refrigerant flow Cooling Heating Discharge pipe thermistor Heat exchanger thermistor Muf...

Page 13: ...F Fan motor MRCW MRM10 MRM20 Magnetic relay N Neutral PCB1 PCB2 Printed circuit board Q1L Overload protector R1T R2T R3T S10 Thermistor S11 S20 S30 S40 S70 S80 S90 S91 HC3 HC4 HL3 HN3 Connector SA1 Su...

Page 14: ...ith operation and ambient conditions 3 The operation noise measuring method is in accordance with JISC9612 Legend 50 60Hz 220 240V Location of microphone Octave band sound pressure level Octave band c...

Page 15: ...G25 35E 3D045140C Outdoor temp CDB Pull down period Indoor temp CWB Notes The graphs are based on the following conditions Equivalent piping length 7 5 m Level difference 0 m Air flow rate high Coolin...

Page 16: ...in Belgium by Lannoo The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this...

Reviews: