6
|
Unit installation
Installer reference guide
26
RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
6 Unit installation
WARNING
Installation shall be done by an installer, the choice of materials and installation shall
comply with the applicable legislation. In Europe, EN378 is the applicable standard.
In this chapter
6.1 Preparing the installation site
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
CAUTION
▪
Check if the installation location can support the unit's weight. Poor installation is
hazardous. It can also cause vibrations or unusual operating noise.
▪
Provide sufficient service space.
▪
Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may
cause vibrations.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Provide sufficient space around the unit for servicing and air circulation.
▪
Avoid areas where flammable gas or product might leak.
▪
Install units, power cables and communication wiring at least 3 m away from
televisions or radios to prevent interference. Depending on the radio waves, a
distance of 3 m may not be sufficient.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).