background image

4 Installation

Installation manual

10

RXA42+50A2V1B

R32 split series

3P517827-2 – 2017.12

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on  the  site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do not touch them with bare hands.

DC+

DC-

b

c

a

d

e

g

f

a

Multimeter (DC voltage range)

b

S80 – reversing solenoid valve lead wire

c

S20 – electronic expansion valve lead wire

d

S40 – thermal overload relay lead wire

e

S90 – thermistor lead wire

f

LED

g

S70 – fan motor lead wire

4.5.1

Guidelines when connecting the electrical
wiring

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M)

1.2~1.3

M4 (earth)

4.5.2

Specifications of standard wiring
components

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with

applicable legislation

Interconnection cable
(indoor↔outdoor)

4-core cable ≥1.5 mm² and

applicable for 220~240 V

Recommended field fuse

13 A

Earth leakage circuit breaker

MUST comply with

applicable legislation

4.5.3

To connect the electrical wiring on the
outdoor unit

1

Open the wire clamp.

2

Connect the interconnection cable and power supply as follows:

50Hz

220-240V

c

d

f

a

e

b

a

Interconnection cable

b

Power supply cable

c

Field fuse

d

Earth leakage circuit breaker

e

Power supply

f

Earth

3

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

4

Install the switch box cover.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn off the power supply before servicing.

▪ Install the switch box cover before turning on the power

supply.

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

Summary of Contents for RXA42A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXA42A2V1B RXA50A2V1B...

Page 2: ...n ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective D...

Page 3: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 4: ...11 5 2 Checklist during commissioning 11 5 3 To perform a test run 11 6 Configuration 11 6 1 To set the facility mode 11 7 Troubleshooting 12 7 1 Fault diagnosis using LED on outdoor unit PCB 12 8 Dis...

Page 5: ...he air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so...

Page 6: ...nce 20 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 12 7 mm 1 2 14 16 mm i i t p p If the temperature is high...

Page 7: ...the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration fie...

Page 8: ...stem with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test...

Page 9: ...4 4 3 To determine the additional refrigerant amount If the total liquid piping length is Then 10 m Do NOT add additional refrigerant If the total liquid piping length is Then 10 m R total length m o...

Page 10: ...NGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DC DC b c a d e g f a Multimeter DC voltage range b S80 reversin...

Page 11: ...arried out according to this document and the applicable legislation between the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might...

Page 12: ...se the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor because...

Page 13: ...anual of the indoor unit Note Forced cooling will stop automatically after around 30 minutes 2 To stop operation sooner press the ON OFF switch INFORMATION If forced cooling is used and the outside te...

Page 14: ...N E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F...

Page 15: ...nsion valve Cooling Heating Refrigerant flow Heat exchanger thermistor 1 2 3 4 1 4 Capillary tube Muffler Receiver gas Filter S1PH Automatic reset High pressure switch 6 4 CuT 4 0 CuT 7 9 CuT 7 9 CuT...

Page 16: ...3P517827 2 2017 12 Copyright 2017 Daikin...

Reviews: