3 Preparation

Installation manual

4

RXA20~35A2V1B

R32 split series

3P517827-1 – 2017.12

3

Preparation

3.1

Preparing the installation site

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

▪ Choose  the  installation  location  with  sufficient  space  for  carrying

the unit in and out of the site.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

>150

>50

>300

(mm)

b

a

>100

>50

>150

>50

b

b

a

>100

b

a

a

b

a

>100

a

Air outlet

b

Air inlet

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

It  is  recommended  to  install  a  baffle  plate  when  the  air  outlet  is
exposed to wind.

It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.

b

a

b

c

a

Baffle plate

b

Prevailing wind direction

c

Air outlet

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

3.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"4.1  Mounting  the

outdoor unit" on page 5

 for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

Summary of Contents for RXA20A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXA20A2V1B RXA25A2V1B RXA35A2V1B...

Page 2: ...s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standa...

Page 3: ...klist before commissioning 10 5 2 Checklist during commissioning 10 5 3 To perform a test run 10 6 Configuration 10 6 1 To set the facility mode 10 7 Troubleshooting 11 7 1 Fault diagnosis using LED o...

Page 4: ...he air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so...

Page 5: ...fference 15 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is...

Page 6: ...outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field su...

Page 7: ...with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solut...

Page 8: ...4 4 3 To determine the additional refrigerant amount If the total liquid piping length is Then 10 m Do NOT add additional refrigerant If the total liquid piping length is Then 10 m R total length m o...

Page 9: ...ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DC DC g h b c d e f a a Multimeter DC voltage range b S70 fan motor lead wire...

Page 10: ...etween the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The s...

Page 11: ...r before removing the refrigerant piping If the compressor is still running and the stop valve is open during pump down air will be sucked into the system Compressor breakdown or damage to the system...

Page 12: ...N E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P517827 1 2017 12 Copyright 2017 Daikin...

Reviews: