Electrical Installation
www.DaikinApplied.com 51
IM 926-3 • ROOFPAK APPLIED SYSTEMS
All Units
The minimum circuit ampacity (wire sizing amps) is shown on
the unit nameplate. Refer to
number of power wires.
Copper wire is required for all conductors. Size wires in
accordance with the ampacity tables in Article 310 of the
National Electrical Code. If long wires are required, it may
be necessary to increase the wire size to prevent excessive
voltage drop. Size wires for a maximum of 3% voltage drop.
Supply voltage must not vary by more than 10% of nameplate.
Phase voltage imbalance must not exceed 2%. (Calculate
the average voltage of the three legs. The leg with voltage
deviating the farthest from the average value must not be more
than 2% away.) Contact the local power company for correction
of improper voltage or phase imbalance.
A ground lug is provided in the control panel for each
disconnect or power block. Size grounding conductor in
accordance with Table 250-95 of the National Electrical Code.
In compliance with the
isolated 115V circuit is provided in the unit to supply the factory
mounted service receptacle outlet and optional unit lights.
This circuit is powered by a field connected 15A, 115V power
supply. Leads are brought into the RFS and RPS units through
a 7/8" knockout in the bottom of the main control panel, near
the power wire entry point.
Figure 69: Typical Power Wire Entrance, Unit View—RPS
015C - 040C Shown (Actual Opening, see Submittal
Documents)
Figure 70: RCS 015C - 030C Power Wiring Connections
Figure 71: RCS 036C and 105C Power Wiring Connections
(Number of Condenser Fans Varies Per Unit Size)
Detail B
12.0
8.8
3.8
0.9 Dia. K.O.
(Qty 4)
3.0 Dia. K.O.
(Qty 3)
6.8
7.6
6.6
Varies
based on
options
Reference from leaving
air end of section
Bottom return
opening
86.5
76.0
3.8
10.0
6.0
20.0
Bottom Supply air opening
1.50 MPT drain
A
10.0
3.8
C
B
C
E
3.8
94.0
11.9
12.9
22.3
17.7
15.3
24.3
Conduit and hub
(shipped with
RCS unit)
Terminal block TB8
for 115V service
receptical circuit
7/8" knockout for
TB8 wire entry
switch DS4
or disconnect
Power block PB4
7/8" knockout for
wire entry (field to cut
larger holes as required
for power wire)
Power block PB4 or
disconnect switch DS4
7/8" knockout for
TB8 wire entry
Terminal aTB8
for 115V service
receptical circuit
7/8" knockout for wire entry
(field to cut larger holes as
required for pwer wire)
Conduit and hub
(shipped with RCS unit)
Summary of Contents for RoofPak RCS Series
Page 129: ......