![background image](http://html1.mh-extra.com/html/daikin/rn50cgxv1/rn50cgxv1_installation-manual_2459871016.webp)
1-15
English
4WV
A
OF
L
N
COMP
L
N
A
4WV
OF
COMP
N
L
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor
Model
Indoor (FCQN)
50E
60E
71E
Outdoor (RYN/RQ)
50C
60C
71C
Voltage range**
Indoor (FCQN)
220-240V/1Ph/50Hz +
!
Outdoor (RYN/RQ)
220-240V/1Ph/50Hz +
!
Power supply cable size*
(mm
2
)
Number of conductors
2.5
3
2.5
3
4.0
3
Interconnection cable size*
(mm
2
)
Number of conductors
2.5
5
2.5
5
2.5
5
Recommended time delay fuse*
(A)
13
18
25
FCQN 100E - RQ 90/100D (1 PH)
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
4WV
OF
COMP
N
OF
4WV
COMP
L
N
N1
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor
FCQN 50/60E - RYN 50/60C (1 PH)
FCQN 71E - RQ 71C (1 PH)
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.