INSTALLATION
MANUAL

MODELS

FCRN50EXV1

RN50C(G)XV1

FCRN60EXV1

RN60C(G)XV1

FCRN71EXV1

RR71C(G)XV1

FCRN100EXV1

RR90D(G)XV1

FCRN125EXV1

RR90D(G)XY1
RR100D(G)XV1

FCQN50EXV1

RR100D(G)XY1

FCQN60EXV1

RR125D(G)XY1

FCQN71EXV1
FCQN100EXV1

RYN50C(G)XV1

FCQN125EXV1

RYN60C(G)XV1
RQ71C(G)XV1
RQ90D(G)XV1
RQ90D(G)XY1
RQ100D(G)XV1
RQ100D(G)XY1
RQ125D(G)XY1

CEILING CASSETTE  
R410A SPLIT TYPE AIR CONDITIONER 
(E Series)

IM-5CKE-0912(0)DAIKIN

Part No.: R08019038169

English

Français

Deutsch

Italiano

Español

Русский

Türkçe

Installation Manual

R410A Split Type Air Conditioner

Manuel D’installation

Climatiseurs Split System R410A

Installationshandbuch

Doppelfunktions-Klimagerät and R410A

Manuale Di Installazione

Condizionatore Split A R410A 

Manual De Instalación

Equipo de air Acondicionado de tipo 

Dividido de R410A

Руководство по установке

R410A разделить Кондиционер 

воздуха типа

Kurulum kılavuzu

R410A Split Tipi Klima

CVR 5CKE-0912(0)DAIKIN-EN.indd   1

CVR 5CKE-0912(0)DAIKIN-EN.indd   1

9/27/12   12:12:39 PM

9/27/12   12:12:39 PM

Summary of Contents for RN50CGXV1

Page 1: ...5CKE 0912 0 DAIKIN Part No R08019038169 English Français Deutsch Italiano Español Русский Türkçe Installation Manual R410A Split Type Air Conditioner Manuel D installation Climatiseurs Split System R410A Installationshandbuch Doppelfunktions Klimagerät and R410A Manuale Di Installazione Condizionatore Split A R410A Manual De Instalación Equipo de air Acondicionado de tipo Dividido de R410A Руковод...

Page 2: ...9 101 113 603 126 60 71C 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S 50C 164 15 34 23 362 73 75 60 71C 164 15 34 23 362 73 75 Dimension Model A B C D E F G H I J K 50 60 71E 820 820 340 300 40 990 990 627 627 607 430 100 125E 820 820 375 335 40 990 990 627 627 607 430 Indoor Unit FCRN FCQN Original Instruction 1 IM 5CKE 0912 0 DAIKIN EN indd 1 1 IM 5CKE 0912 0 DAIKI...

Page 3: ...e in mm I J J D M B G O Dimension Model A B C D E F G H I J K L M N O 90 100 125D 1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28 N N K A L E F H C 1 IM 5CKE 0912 0 DAIKIN EN indd 2 1 IM 5CKE 0912 0 DAIKIN EN indd 2 9 28 12 2 04 14 PM 9 28 12 2 04 14 PM ...

Page 4: ...re Do not overcharge the unit This unit is factory pre charged Overcharge will cause over current or damage to the compressor Ensure that the unit s panel is closed after service or installation Unsecured panels will cause the unit to operate noisily Sharp edges and coil surfaces are potential locations which may cause injury hazards Avoid from being in contact with these places Before turning off...

Page 5: ... e g onto the inside of the service cover 1 factory refrigerant charge of the product see unit name plate 2 2 additional refrigerant amount charged in the field 3 total refrigerant charge 4 contains fluorinated greenhouse gases covered by the Kyoto Protocol 5 outdoor unit 6 refrigerant cylinder and manifold for charging 2 In case of multiple indoor systems only 1 label must be adhered mentioning t...

Page 6: ... or when moving it after opening Do not move the unit from packaging while moving until it reaches the installation site Use safe material or protection plates when unpacking it or lifting it to avoid damage or scratches to the unit Drain Piping Front Panel Air Filter behind the grille Air Intake Grille Air Discharge Air Discharge Louver Air Intake Air Intake Thermal Insulation Wrap the insulated ...

Page 7: ...t on the ceiling and fix the hanging rod The installation template is extended according to temperature and humidity Check on dimensions in use The dimensions of the installation template are the same as those of the ceiling opening dimensions Before ceiling laminating work is completed be sure to fit the installation template to the indoor unit NOTE Be sure to discuss the ceiling drilling work wi...

Page 8: ...n connector on the indoor unit Drain Test NOTE This Indoor Unit uses a drain pump for condensed water drainage Install the unit horizontally to prevent water leakage or condensation around the air outlet Panel Installation The front panel can only be fitted in one direction follow the piping direction Follow piping arrow sticker on front panel Be sure to remove the installation template before ins...

Page 9: ...ed off before servicing the unit Use screwdriver to unlock the screw on the cover lock grille Remove the cover lock grille and open the intake grille for the service purpose Install the intake grille and screw the cover lock grille after service and make sure the unit is proper install 1 2 3 4 Frame Intake Grille Cover Lock Grille 2pcs Screw 4 x 6 2pcs Indoor Unit Cool Air Ceiling Board Panel Air ...

Page 10: ...ove wire cover by removing 2 screws as shown in Figure C Wires will go through the hole as shown in Figure D and E respectively without crossing the height of the hole After that wire cover will be assembled back to close the wire 1 2 3 Figure B Figure C Figure D Figure E 1 IM 5CKE 0912 0 DAIKIN EN indd 9 1 IM 5CKE 0912 0 DAIKIN EN indd 9 9 28 12 2 04 17 PM 9 28 12 2 04 17 PM ...

Page 11: ... Ensure that there is no obstruction of air flow into or out of the unit Remove obstacles which block air intake or discharge The location must be well ventilated so that the unit can draw in and distribute plenty of air thus lowering the condensing temperature A place capable of bearing the weight of the outdoor unit and isolating noise and vibration A place protected from the direct sunlight Oth...

Page 12: ...Air Inlet Air Discharge A B Obstacle Obstacle MADE IN MALAYSIA Service Space Obstacle C D Obstacle BASE A DRAIN ELBOW PLUG DRAIN ELBOW Model Indoor FCRN FCQN 50E 60E 71E 100E 100E 125E Outdoor RN RR RYN RQ 50C 60C 71C 90D 100D 125D Max allowable length m 15 15 15 45 45 45 Max allowable elevation m 8 8 8 25 25 25 Liquid pipe size mm in 6 35 1 4 6 35 1 4 9 52 3 8 9 52 3 8 9 52 3 8 9 52 3 8 Gas pipe ...

Page 13: ...th the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool Refer Figure III Fix the pipe firmly on the flare die Match the centers of both the flare die and the flaring punch and then tighten the flaring punch fully Piping Connection To The Units Align the center of the piping and tighten...

Page 14: ...l Block Power Supply Cable ELECTRICAL WIRING CONNECTION IMPORTANT These values are for information only They should be checked and selected to comply with local and or national codes and regulations They are also subject to the type of installation and size of conductors The appropriate voltage range should be checked with data label on the unit FCRN 50 60E RN 50 60C 1 PH FCRN 71E RR 71C 1 PH Ther...

Page 15: ...4 2 5 4 Recommended time delay fuse A 25 30 Model Indoor FCRN 100E 125E Outdoor RR 100D 125D Voltage range Indoor FCRN 220 240V 1Ph 50Hz Outdoor RR 380 415V 3N 50Hz Power supply cable size mm2 Number of conductors 2 5 5 4 0 5 Interconnection cable size mm2 Number of conductors 1 5 4 1 5 4 Recommended time delay fuse A 13 18 FCRN 100 125E RR 100 125D 3 PH There must be an all pole disconnection in ...

Page 16: ...r of conductors 2 5 5 2 5 5 2 5 5 Recommended time delay fuse A 13 18 25 FCQN 100E RQ 90 100D 1 PH There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm 4WV OF COMP N OF 4WV COMP L N N1 Indoor Unit Terminal Block Interconnection Cable Outdoor Unit Terminal Block Power Supply Cable Outdoor Coil Sensor FCQN 50 60E RYN 50 60C 1 PH FCQN 71E RQ 71C 1 PH T...

Page 17: ...oor Unit Terminal Block Power Supply Cable Outdoor Coil Sensor FCQN 100 125E RQ 100 125D 3 PH Model Indoor FCQN 100E 125E Outdoor RQ 100D 125D Voltage range Indoor FCQN 220 240V 1Ph 50Hz Outdoor RQ 380 415V 3N 50Hz Power supply cable size mm2 Number of conductors 2 5 5 2 5 5 Interconnection cable size mm2 Number of conductors 1 5 3 4 1 5 3 4 Recommended time delay fuse A 13 18 There must be an all...

Page 18: ... ozone layer The working pressure of this new refrigerant is 1 6 times higher than conventional refrigerant R22 thus proper installation servicing is essential Never use refrigerant other than R410Ain an air conditioner which is designed to operate with R410A POE or PVE oil is used as lubricant for R410Acompressor which is different from the mineral oil used for R22 compressor Duringinstallationor...

Page 19: ...ti clockwise direction with 4mm key for hexagon sacked screw Charge Operation This operation must be done by using a gas cylinder and a precise weighing machine The additional charge is topped up into the outdoor unit using the suction valve via the service port Remove the service port cap Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank a...

Page 20: ...first few hours or the damage done during field charging may show up some time later Other typical field charging problems include undercharging overcharging moisture or air in the system etc In time each one of these problems can cause compressor failure Minimal equipment is required for field charging The minimum equipment required to do a satisfactory job is Set of service gauges 1 Vacuum gauge...

Page 21: ...nd Manifold valve A are both open A There are many ways of charging liquid in a controlled manner into the suction side Use valve A on the manifold gauge set Use the valve on the refrigerant cylinder Charge through a Shredder valve Use a hose with a Shredder valve depressor Charge into the suction side at some distance from the compressor All of the above 1 2 3 4 5 6 Charging procedures Three phas...

Page 22: ...ct Keep the introduction of fresh air intake within 20 of total air flow Also provide a chamber and use a booster fan Sealing Material It is possible to seal one of the four air discharge outlet sealing two or more air discharge outlet could cause a malfunction Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air outlet The sealing...

Page 23: ...ror Code 1 Room Sensor Open or Short Blink 1 time Blink Fan Blink E1 2 Indoor Coil Sensor Open Blink 2 times Blink Sleep Blink E2 3 Outdoor Coil Sensor Open Blink 3 times Blink Dry Blink E3 4 Compressor Overload Indoor Coil Sensor Short Outdoor Coil Sensor Short Blink 1 time Blink Cool Blink E4 5 Low Refrigerant Charge Gas Leak Outdoor Abnormal Blink 3 times Blink Cool Dry Blink E5 6 Water Pump Fa...

Page 24: ...The unit with Scroll Compressor can only rotate in one direction For this reason a protective device phase protector is fitted to prevent incorrect wiring of the electrical phases When the three phases are not connected correctly the phase protector operates and the unit will not start This device is located in the control box of the outdoor unit The following table shows the LED indicator light f...

Page 25: ...to the unit Check the following fault conditions and causes for some simple troubleshooting tips Fault Causes Action The compressor does not start operate after 3 minutes from starting the air conditioner unit 1 Protection against frequent starting Wait for 3 to 4 minutes for the compressor to start operating The air conditioner unit does not operate 2 Power failure or the fuse need to be replaced...

Page 26: ... traduzioni in altre lingue la versione in lingua inglese prevale Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica En caso de conflicto en la interpretación de este manual y en su traducción a cualquier idioma prevalecerá la versión inglesa El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y d...