
SiBE041101
Troubleshooting
Service Diagnosis
80
4. Troubleshooting
4.1
Error Codes and Description
★
: Displayed only when system-down occurs.
Error Codes
Description
Reference
Page
System
00
Normal
—
U0
★
Refrigerant shortage
117
U2
Low-voltage detection or over-voltage detection
120
U4
Signal transmission error (between indoor unit and outdoor unit)
87
UA
Unspecified voltage (between indoor unit and outdoor unit)
88
Indoor
Unit
A1
Indoor unit PCB abnormality
81
A5
Freeze-up protection control or heating peak-cut control
82
A6
Fan motor (DC motor) or related abnormality
84
C4
Indoor heat exchanger thermistor or related abnormality
86
C9
Room temperature thermistor or related abnormality
86
Outdoor
Unit
E1
Outdoor unit PCB abnormality
89
E5
★
OL activation (compressor overload)
92
E6
★
Compressor lock
93
E7
DC fan lock
94
E8
Input overcurrent detection
95
EA
Four way valve abnormality
96
F3
Discharge pipe temperature control
98
F6
High pressure control in cooling
100
H0
Compressor system sensor abnormality
101
H6
Position sensor abnormality
103
H8
DC voltage / current sensor abnormality (20/25/35/42 class)
106
CT or related abnormality (50 class)
107
H9
Outdoor temperature thermistor or related abnormality
109
J3
Discharge pipe thermistor or related abnormality
109
J6
Outdoor heat exchanger thermistor or related abnormality
109
L3
Electrical box temperature rise
111
L4
Radiation fin temperature rise
113
L5
Output overcurrent detection
115
P4
Radiation fin thermistor or related abnormality
109
U7
Signal transmission error on outdoor unit PCB (50 class only)
122