Purging air and checking gas leakage

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• If using additional refrigerant, perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

*1. Pipe length vs. vacuum pump run time.  

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.  

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.  
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

Compound 
pressure gauge

Pressure 
metre

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

01_EN_3P203824-12L.fm  Page 6  Thursday, October 18, 2012  10:39 AM

Summary of Contents for RKS42J2V1B

Page 1: ...lit serisi Installationsanleitung Split Baureihe R410A Manuel d installation Série split R410A Montagehandleiding R410A Split systeem Manual de instalación Serie Split R410A Manuale d installazione Serie Multiambienti R410A Εγχειρßδιο εγκατÜστασηò διαιροýìενηò σειρÜò R410A Manual de Instalação Série split R410A Рóêоводство по монтажó Серия R410A с раздельной óстановêой 00_CV_3P203824 12L fm Page 1...

Page 2: ...DUSTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 13E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS42J2V1B RKS42J2V1B KEMA Quality B V 74736 KRQ EMC97 4957 3SB64564 13E fm Page 1 Tuesday November 9 2010 11 56 AM ...

Page 3: ...35 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 19F Shinri Sada Manager Quality Control Department RXS42K2V1B Machinery 2006 42 EC Electromagnetic Compatibility 2004 108 EC Low Voltage 2006 95 EC 3SB65451 19F fm Page 1 Tuesday October 16 2012 5 42 PM ...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM ...

Page 5: ...ls If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakage Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker When installing or relocating th...

Page 6: ...8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow ...

Page 7: ...ditional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it ...

Page 8: ...door Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of at least 30mm in height und...

Page 9: ...re nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly at right angles Remove burrs Set exactly at the position shown below A Flaring Die Check Flare s inner surface must be flaw free The pipe end must be evenly flared in a perfect circle Make sure that...

Page 10: ... valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound p...

Page 11: ... dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Thickness 10mm Min 30mm or more Thickness 0 8mm C1220T O Filling a cylinder with an attached siphon Stand the cylinder upright when filling There is a siphon p...

Page 12: ...al operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Press both of TEMP button and MODE button at the same time 4 Press MODE button twice will be displayed and the unit will enter trial operation Trial operation will stop automatically after around 30 minutes ...

Page 13: ...ere the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew jumping from the indoor unit outlet vent...

Page 14: ...ge systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoidable reasons be sure to observe the following instruction Place the round crimp style term...

Page 15: ...on in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air c...

Page 16: ... 1210 HT 3P203824 12L M12B149 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 12L fm Page 2 Thursday October 18 2012 10 38 AM ...

Reviews: