![background image](http://html1.mh-extra.com/html/daikin/rkm28nv2s/rkm28nv2s_service-manual_2459838009.webp)
Si001271EE
Electrical Box
Removal Procedure
7
4
Disconnect the
connector [S70].
[S70]: fan motor
5
Release the fan motor
lead wire from the 5
hooks.
+
: When reassembling, do not
use these 2 hooks.
6
Disconnect the
connectors of the front
side.
[S20]: electronic expansion
valve coil
[S40]: overload protector
[S80]: four way valve coil
[S90]: thermistors
The cooling only models
have no harness for [S80].
When reassembling, insert
each clamp into the hole as
below.
Step
Procedure
Points
(R7008)
[S70]
+
Fan motor
lead wire
(R18779)
Hook
Hook
(R17577)
Clamp
[S80]
[S40] [S20]
[S90]
Thermistor ASSY harness
(R22515)
Electronic expansion
valve coil harness