Symptom-based Troubleshooting
SiUS371901EB
271
Part 6 Service Diagnosis
1.2 With
Gas
Furnace
1.3 Gas Furnace Lockout Reset
Furnace lockout is characterized by a non-functioning furnace (circulator blower may be running
continuously) providing a diagnostic LED code located on the furnace board.
Lockout results when a furnace control detects abnormal conditions. If the furnace is in "lockout",
the following methods can be used to clear the error.
a. Turn the remote controller OFF to clear the error. If the error is not cleared, proceed to next step.
b. Heat pump lockout conditions are met.
c. Set the setting temperature to maximum, then turn the remote controller ON.
d. Turn the remote controller OFF.
e. Turn the remote controller ON after around 15 seconds from procedure d.
The procedures c, d, and e will not work during certain outdoor unit operations, i.e. defrost, startup,
compressor stop, service mode etc.
If the LED of the
ON/OFF
button is flashing when you turn the remote controller ON, you cannot
clear the error with the method above. In that case, the error must be cleared using the gas
furnace. Refer to the gas furnace operation manual for more details.
Symptom
Supposed Cause
1
The gas furnace does not start operation.
The gas furnace does not start operation while the compressor
is during operation or under stop-control, or right after defrost
IN or defrost OUT. Wait until the operation becomes stable.
2
Operation does not switch from heat pump to gas furnace in
spite of low room temperature. Operation does not switch from
gas furnace to heat pump even though the room temperature
is nearing the set temperature.
This function is performed only with outdoor units which
support automatic switching between gas furnace and heat
pump interlocking with room temperature.
Some models are enabled to support automatic switching
between gas furnace and heat pump interlocking with outdoor
air temperature by setting heat pump lockout on an outdoor
unit side. However, the compressor stops while gas furnace is
during operation.
3
AA-03
(Gas furnace abnormality) is indicated on the remote
controller while no error is indicated on the PCB of the gas
furnace.
In some cases of gas furnace abnormality, error indication on
the remote controller is retained even after the abnormality is
removed. Execute combustion heating operation once or reset
the power source.
4
The airflow rate indication on the remote controller is not
consistent with the actual airflow rate of the indoor unit.
The airflow rate of the indoor unit during gas furnace
combustion heating depends on the intensity of combustion.
Therefore, the airflow rate of the indoor unit does not reflect the
airflow setting of the remote controller.
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...