Field Setting from Outdoor Unit
SiUS371901EB
243
Part 5 Field Settings and Test Operation
[2-31]:
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 2. The level is according to the table.
Default value: 1
Change [2-31] to 1, 2 or 3 in function of required limitation.
Value
[2-31]
Power consumption limitation (approximately)
1 (default)
40%
2
50%
3
55%
[2-32]:
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value: 0 (OFF).
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Change [2-32]: 0,1 or 2 in function of required limitation.
[2-34]:
Indoor fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air
temperature for energy saving
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units capacity
≥
130%.
1
In heating mode, fan speed is limited to L tap when indoor
units capacity
≥
130%.
2
Fan speed follows the setting of remote controllers (not
limited by indoor units connection capacity).
3
Limited in cooling when Ta < 29.5°C (85.1°F) and Indoor
condition is in condition A (
∗
1) Returned when Ta > 32.5°C
(90.5°F)
or Indoor condition is in condition B (
∗
2)
4
Limited in cooling when Ta < 23.5°C (74.3°F) and Indoor
condition is in condition A (
∗
1) Returned when Ta > 26.5°C
(79.7°F)
or Indoor condition is in condition B (
∗
2)
5
Limited in cooling when Ta < 19.3°C (66.7°F) and Indoor
condition is in condition A (
∗
1) Returned when Ta > 22.3°C
(72.1°F)
or Indoor condition is in condition B (
∗
2)
6
Limited in cooling when Ta < 29.5°C (85.1°F) Returned
when Ta > 32.5°C (90.5°F)
7
Limited in cooling when Ta < 23.5°C (74.3°F) Returned
when Ta > 26.5°C (79.7°F)
8
Limited in cooling when Ta < 19.3°C (66.7°F) Returned
when Ta > 22.3°C (72.1°F)
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...