DPS 003–015 (only) Ignition Control Module for Staged Gas Furnace
Figure 52: Typical Staged Gas Furnace Electrical Schematic with Sensor
Ignition Control Module LED Diagnostics
The following LED indicators can be used to diagnose faults
associated with the staged gas furnace.
Table 21: LED Indicator and Fault Conditions
Indicator
Fault Condition
Steady Off
No power or control hardware fault
Steady On
Power applied, control OK
1 Flash
Combustion fan motor energized, pressure switch open
2 Flashes
Combustion fan motor off, pressure switch closed
3 Flashes
Ignition lockout from too many trials
4 Flashes
Ignition lockout from too many flame losses within single
call for heat
5 Flashes
Control hardware fault detected