Daikin RDXYQ8T7V1B Installation Manual Download Page 6

5 Installation

Installation manual

6

8T7V1B*

VRV IV heat exchanger unit for indoor installation

4P408444-1B – 2016.04

4.2

Preparing electrical wiring

4.2.1

Safety device requirements

NOTICE

When  using  residual  current  operated  circuit  breakers,  be
sure  to  use  a  high-speed  type  300  mA  rated  residual
operating current.

Power supply: Heat exchanger unit

The  power  supply  must  be  protected  with  the  required  safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.

Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.

Model

Minimum circuit

ampacity

Recommended

fuses

RDXYQ5

4.6 A

10 A

RDXYQ8

7.0 A

10 A

▪ Phase and frequency: 1~ 50 Hz

▪ Voltage: 220-240 V

Transmission wiring

Transmission line section:

Transmission wiring

Sh shielded cable (2

wires)

Vinyl cords

0.75~1.25 mm²

(using shielded cable for the
transmission wiring is mandatory
for 5 HP, and optional for 8 HP)

Maximum wiring length

(= distance between compressor
unit and furthest indoor unit)

300 m

Total wiring length

(= distance between compressor
unit and all indoor units, and
between compressor unit and
heat exchanger unit)

600 m

If the total transmission wiring exceeds these limits, it may
result in communication error.

5

Installation

5.1

Opening the units

5.1.1

To open the switch box cover of the heat
exchanger unit

DANGER: RISK OF ELECTROCUTION

5.2

Mounting the heat exchanger unit

5.2.1

Guidelines when installing the heat
exchanger unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Suspension  bolts.

  Use  suspension  bolts  for  installation.  Check

whether  the  ceiling  is  strong  enough  to  support  the  weight  of  the
unit. If there is a risk, reinforce the ceiling before installing the unit.
Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
by using a nut and washer from the upper and lower sides of the
hanger bracket.

a1

b

b

a2

c

1497

(mm)

705

255

84

a1

Nut

a2

Double nut

b

Washer

c

Hanger bracket

Drain  water  flow.

  Make  sure  drain  water  flows  to  the  drain  pipe

connection.

0~2°

0~2°

A

A

B

B

a

a

a

a

Drain pipe connection

5.2.2

Guidelines when installing the ducting

The ducting is to be field supplied.

Slope.

 Make sure the ducting slopes down to prevent water from

flowing into the heat exchanger unit.

a

b

a

a

Ducting

b

Heat exchanger unit

Summary of Contents for RDXYQ8T7V1B

Page 1: ...Installation manual VRV IV heat exchanger unit for indoor installation English Installation manual VRV IV heat exchanger unit for indoor installation RDXYQ5T7V1B RDXYQ8T7V1B...

Page 2: ...iten befinden sich entsprechend Artikel 1 2f des PED au erhalb der Reichweite Risikoart H Siehe auch n chste Seite tel que d fini dans A et valu positivement par B conform ment au Certificat C tel que...

Page 3: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim...

Page 4: ...arget audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documenta...

Page 5: ...ing units and options 3 3 1 Possible options for the compressor unit and heat exchanger unit For more possible options see the installer and user reference guide Drain pan heater EKDPH1RDX When Instal...

Page 6: ...unit and all indoor units and between compressor unit and heat exchanger unit 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Openin...

Page 7: ...Discharge ducting 5 2 3 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the heat exc...

Page 8: ...NG 5 3 1 To connect the refrigerant piping to the heat exchanger unit 1 Remove the cover 2 Remove the 2 insulation pieces 3 Put a wet cloth in front of the EPS to protect the drain pan 4 Braze the liq...

Page 9: ...F2 F1 F2 F1 F2 b X2M X2M X2M X1M A1P RKXYQ5 RDXYQ5 TO OUT D TO IN D F1 F2 F1 F2 a1 a2 a2 a F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 b a RKXYQ8 RDXYQ8 TO OUT D TO IN D F1 F2 F1 F2 8 HP 5...

Page 10: ...iring depending on model PCB Legend for wiring diagram 5 8 HP A1P Printed circuit board main A2P Printed circuit board adapter C1 Capacitor A1P E1H Drain pan heater optional F1U Fuse F 1 A 250 V optio...

Page 11: ......

Page 12: ...4P408444 1 B 0000000 4P408444 1B 2016 04 Copyright 2015 Daikin...

Reviews: