Si011360EC

Compressor ASSY

Removal Procedure

11

5. Compressor ASSY

Warning

Š

Be sure to wait for 10 minutes or more after turning off all power supplies before 
disassembling work.

Š

Be careful not to get yourself burnt with the pipes and other parts that are heated by 
the gas brazing machine.

Š

If the refrigerant gas leaks during work, ventilate the room. (If the refrigerant gas is 
exposed to flames, toxic gas may be generated.)

Š

Since it may happen that the refrigerant oil in the compressor catches fire, prepare wet 
cloth so as to extinguish fire immediately.

Caution

Š

From the viewpoint of global environment protection, do not discharge the refrigerant 
gas in the atmosphere. Make sure to collect all the refrigerant gas.

Š

Restore the piping by non-oxidation brazing.

Note

Š

Before working, make sure that the refrigerant gas is empty in the circuit.

Š

Be sure to apply nitrogen replacement when heating up the brazed part.

Š

Do not use a metal saw for cutting pipes by all means because the sawdust comes into 
the circuit.

Š

When withdrawing the pipes, be careful not to pinch them firmly with pliers. The pipes 
may get deformed.

Š

Provide a protective sheet or a steel plate so that the brazing flame cannot influence 
peripheries.

Š

Be careful so as not to burn the compressor terminals, the name plate, the outdoor 
heat exchanger fin.

Š

In case of difficulty with gas brazing machine

1. Disconnect the brazed part where is easy to disconnect and restore.
2. Cut pipes on the main unit with a tube cutter in order to make it easy to disconnect.

Step

Procedure

Points

1

2

Remove the nut.

Remove the terminal 
cover.

„

The shape of the terminal 
cover varies depending on 
the model.

(R19497)

Nut

Terminal 
cover

Summary of Contents for RC50PRV16

Page 1: ...4 2 5 0 6 0 kW Class REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Non Inverter Pair Type Si011360EC...

Page 2: ...1625 RF50RRV161 RQ60RRV1625 RC42RRV162 RF60RRV161 RC50RRV161 RF50RRV1615 RQA50QRV16 RC50RRV162 RF60RRV1615 RQA60QRV16 RC60RRV162 RC42RRV1625 RFA50QRV16 RQA50RRV162 RC50RRV1615 RFA60QRV16 RQA60RRV162 R...

Page 3: ...dure 1 Table of Contents 1 Outer Panels 2 2 Outdoor Fan Fan Motor 3 3 Electrical Component ASSY 5 4 Sound Blanket Capillary Tube 9 5 Compressor ASSY 11 Note The illustrations may be slightly different...

Page 4: ...rews and then the top panel Remove the 7 screws of the front panel 3 4 Unfasten the 2 right side hooks and remove the front panel Remove the screw and then the discharge grille The discharge grille ha...

Page 5: ...apacitor C1 Pull out the terminal 3 front black from the terminal board X1M Release the fan motor lead wire from the hook 4 Remove the nut and then the outdoor fan Nut size M6 When reassembling align...

Page 6: ...ut the fan motor lead wire through the back of the fan motor to avoid any entanglement with the outdoor fan When reassembling fit the 2 lower hooks into the bottom frame 6 Unfasten the 2 hooks and rel...

Page 7: ...s 1 Remove the right side panel The stop valve cover has 3 hooks 1 Remove the screw and then the stop valve cover 2 3 Remove the 3 screws and remove the wire fixture Remove the 7 screws on the termina...

Page 8: ...side lower Remove the 3 screws on the rear side 7 Unfasten the hook on the back When reassembling make sure the hook is securely fastened 8 Remove the right side panel The right side panel has 2 hook...

Page 9: ...nal board X1M Capacitor C1 Pattern 1 RC50PRV16 RQ60PRV16 Step Procedure Points Capacitor Terminal board R20992 from compressor R blue from compressor S red R23477 from terminal board 2 back blue from...

Page 10: ...Series RF Series RQ50PRV16 RQ Q Series RQ R Series RUF Series 3 Remove the screw and then the electrical component ASSY Step Procedure Points from compressor S red from compressor R blue from terminal...

Page 11: ...e to apply nitrogen replacement when heating up the brazed part Do not use a metal saw for cutting pipes by all means because the sawdust comes into the circuit When withdrawing the pipes be careful n...

Page 12: ...Remove the protection net 4 5 Remove the putties if any Heat up the 2 brazed parts and remove the capillary tube The shape of the capillary tube varies depending on the model Step Procedure Points Pr...

Page 13: ...y non oxidation brazing Note Before working make sure that the refrigerant gas is empty in the circuit Be sure to apply nitrogen replacement when heating up the brazed part Do not use a metal saw for...

Page 14: ...3 4 Disconnect the compressor lead wires Remove the gasket Step Procedure Points Gasket Compressor lead wire R19498 Pattern 1 Pattern 2 C U white S V red R W blue C U white S V red R W blue Pattern 3...

Page 15: ...essor 7 8 9 10 Remove the putties if any Heat up the brazed part of the discharge side pipe and disconnect Heat up the brazed part of the suction side pipe and disconnect Lift the compressor ASSY up a...

Page 16: ...60QRV16 RF50 60QRV16 RF50QRV161 RFA50 60QRV16 RFD50 60QRV16 RQ50 60QRV16 RQA50 60QRV16 RQD50 60QRV16 06 2016 Si011360EC Model addition RC50 60QRV1615 RC42 50 60RRV162 RC50RRV161 RC42 60RRV1625 RC50RR...

Page 17: ...ories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and acc...

Reviews: