Si20-701_B
Troubleshooting by Remote Controller
88
Remote Controller Display
A6
Applicable Models
FCQ, FHQ, FAQ
Method of Error Detection
Detection of abnormal fan speed by signal from the fan
motor
Error Decision Conditions
The error is generated when the rotation speed of the fan
motor are not detected while the output voltage to the fan
is at its maximum.
For FCQ-C7, FAQ-BU
When fan speed does not increase
Supposed Causes
Defective indoor unit fan motor
Breaking or disconnection of wire
Defective contact
Defective indoor unit PCB
For FCQ-C7, FAQ-BU
Disconnection, short circuit or disengagement of
connector in fan motor harness
Defective fan motor (disconnection, poor insulation)
Abnormal signal from fan motor (defective circuit)
Defective Indoor unit PCB
Instantaneous fluctuation of power supply voltage
Fan motor lock
(Caused by motor or other external factors)
Fan does not turn due to a tangle of foreign matters.
The connector between the high-voltage PCB and the
low-voltage PCB is disconnected.