background image

27

7

• Split Sky Air • Outdoor Units

27

• Outdoor Units • R-410A • RR-B7

7

Wiring diagram

7 - 2

External connection diagram

R(Q)(R)71-125B7

4TW26329-7

I

Pair

II

Twin

III

Triple

M Master

S

Slave

1

Earth leak detector

2

Fuse

3

Remote controller

Summary of Contents for PR100B7V3B

Page 1: ...RR B7 Pair Twin Triple Double Twin Application technical data Split Sky Air air conditioning systems ...

Page 2: ... the quality of the environment Daikin Europe N V is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard ISO9001 pertains to quality assurance regarding design development manufacturing as well as to services related to the product Daikin units comply with the European regulations that guarantee the safety of the product Daikin Europe N V participates in the ...

Page 3: ...ttings 9 3 Options 10 4 Capacity tables 11 Combination table 11 Cooling capacity tables 12 Cooling capacity tables simultaneous operation 18 5 Dimensional drawing centre of gravity 19 Dimensional drawing 19 Centre of gravity 21 6 Piping diagram 23 7 Wiring diagram 25 Wiring diagram 25 External connection diagram 27 8 Sound data 28 Sound pressure spectrum 28 Sound power spectrum 29 9 Operation rang...

Page 4: ...d easily on a roof or terrace or simply placed against an outside wall Outdoor units are fitted with a scroll compressor renowned for low noise and high energy efficiency The piping connections can be accessed from underneath front side or rear The sevice valves are hidden inside the casing A special acryl precoated fin for anti corrosion treatment on the heat exchanger ensures greater resistance ...

Page 5: ...nt PE Fan Type Direct Drive Propeller Discharge direction Horizontal Quantity 1 1 1 1 2 Air Flow Rate nominal Cooling m3 min 48 0 48 0 55 0 55 0 89 0 Motor Quantity 1 1 1 1 1 Model P47L11S Position Lower Motor Speed nominal at 230V Steps 3 3 3 3 3 Fan Motor Output W 65 65 65 65 85 Drive direct drive Position Upper Motor Speed nominal at 230V Steps 3 Fan Motor Output W 65 Drive direct drive Compres...

Page 6: ...0 30 Installation height difference Maximum m 30 0 30 0 30 0 30 0 30 0 Max internunit level difference m 0 5 0 5 0 5 0 5 0 5 Heat Insulation Both liquid and gas pipes Defrost Method Reversed cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method None Safety Devices Reverse phase protector PC board fuse Overcurrent relay compressor Low pressure switch High press...

Page 7: ...es earth wire included Power Supply Intake Outdoor unit only NOTES 1 Sound pressure level is a relative value depending on the distance and acoustic environment For more details please refer to sound level drawings of this chapter 2 The sound power level is an absolute value indicating the power which a sound source generates 3 Sound values are measured in a semi anechoic room 4 Heating capacity i...

Page 8: ...7W1B 50 400 230 8 1 11 5 16 41 1 5 3 0 065 0 6 0 125 0 9 SYMBOLS MCA Min Circuit Amps TOCA Total Over Current Amps MFA Max Fuse Amps See note 7 LRA Locked Rotor Amps RLA Rated Load Amps OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps kW Fan Motor Rated Output NOTES 1 RLA is based on the following conditions Indoor temperature 27 CDB 19 5 CWB Outdoor temperature 35 CDB 2 TOCA means th...

Page 9: ...connections see http www daikineurope com extranet select Daikin Documentation and select conditional connection the requested product type and English from the drop down lists click the search button Finally click on the document title of your choice Unit combination Power supply Compressor OFM IFM Indoor unit Outdoor unit Hz Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA FCQ100 RR100B7V3...

Page 10: ...ard fuse rating Min 16A 6 Select wire size based on the larger value of MCA or TOCA 7 Instead of fuse use circuit breaker 8 For more details concerning conditional connections see http www daikineurope com extranet select Daikin Documentation and select conditional connection the requested product type and English from the drop down lists click the search button Finally click on the document title...

Page 11: ... RQ100B7V3B RR71B7V3B RR100B7V3B RQ71B7W1B RQ100B7W1B RQ125B7W1B RR71B7W1B RR100B7W1B RR125B7W1B Fan motor thermal protector Off 135 5 C On 95 15 C HPS Off 4 15 0 0 10 Mpa LPS Max discharge temperature By thermistor and software control Overcurrent relay By overcurrent sensor and software control Off 0 03 0 02 0 02 Mpa On 3 2 0 15 0 15 Mpa On 0 05 0 03 0 03 Mpa ...

Page 12: ... 27 3 3 Options Available option for RQ71 125B7 V3 W1 B and RR71 125B7 V3 W1 B 3TW26329 1 Name of option Kit name RQ71B7 RQ100B7 RQ125B7 RR71B7 RR100B7 RR125B7 Central drain plug KKPJ5F180 Refrigerant branch piping Twin KHRQ22M20TA7 Triple KHRQ127H7 KHRQ127H7 ...

Page 13: ...ired Refnet kits mentioned that are necessary to install the combination 5 For unit specification of the outdoor units and the indoor units refer to the unit sepcifications mentioned for pair systems 6 Nominal cooling capacities are based on the following conditions indoor air temperature 27 CDB 19 CWB outdoor temperature 35 CDB Nominal heating capacities are based on the following conditions indo...

Page 14: ...2 83 14 0 20 0 6 6 4 9 1 84 6 5 4 8 2 00 6 0 4 7 2 24 5 9 4 6 2 40 5 5 4 5 2 64 5 2 4 1 2 88 16 0 22 0 7 2 5 0 1 88 7 0 4 9 2 04 6 5 4 8 2 28 6 3 4 7 2 45 6 0 4 6 2 69 5 4 4 2 2 93 18 0 25 0 7 7 5 2 1 92 7 5 5 0 2 09 7 2 4 9 2 34 6 8 4 8 2 50 6 4 4 6 2 76 5 9 4 4 3 01 19 0 27 0 8 0 5 3 1 94 7 7 5 2 2 11 7 3 5 0 2 36 7 1 4 8 2 53 6 6 4 7 2 78 6 1 4 5 3 04 19 5 27 0 8 0 5 3 1 95 7 9 5 2 2 12 7 4 5 0...

Page 15: ...r fan motor Caution TC and SHC are shown by kW V1 V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 29 x 60 x AFR m3 min x 1 BF x DB EDB 860 Add SHC to SHC if SHC TC then TC equal SHC 4 Direct interpolation is permissible Do not extr...

Page 16: ...oor fan motor Caution TC and SHC are shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 29 x 60 x AFR m3 min x 1 BF x DB EDB 860 Add SHC to SHC if SHC TC then TC equal SHC 4 Direct interpolation is permissible Do not extra...

Page 17: ...2 7 4 4 9 2 49 7 2 4 7 2 67 6 7 4 6 2 94 6 2 4 4 3 20 22 0 30 0 8 7 5 3 2 09 8 5 5 2 2 27 8 0 5 1 2 54 7 9 4 8 2 72 7 4 4 7 2 99 6 7 4 4 3 27 24 0 32 0 9 4 5 3 2 11 9 1 5 2 2 29 8 6 5 1 2 57 8 4 4 9 2 75 8 0 4 7 3 02 7 3 4 4 3 30 100 12 0 18 0 8 4 7 0 2 51 8 3 6 9 2 78 8 1 6 7 3 14 7 8 6 6 3 32 7 5 6 2 3 68 6 8 5 9 4 13 14 0 20 0 8 9 7 0 2 56 8 8 6 9 2 83 8 7 6 7 3 20 8 4 6 6 3 38 7 8 6 2 3 75 7 4...

Page 18: ... 2 22 7 4 4 9 2 48 7 2 4 7 2 66 6 7 4 6 2 92 6 2 4 4 3 19 22 0 30 0 8 7 5 3 2 08 8 5 5 2 2 26 8 0 5 1 2 53 7 9 4 8 2 71 7 4 4 7 2 98 6 7 4 4 3 25 24 0 32 0 9 4 5 3 2 10 9 1 5 2 2 28 8 6 5 1 2 56 8 4 4 9 2 74 8 0 4 7 3 01 7 3 4 4 3 29 100 12 0 18 0 8 2 6 8 2 60 8 1 6 7 2 88 7 9 6 5 3 25 7 6 6 4 3 43 7 3 6 0 3 81 6 6 5 7 4 27 14 0 20 0 8 7 6 8 2 65 8 6 6 7 2 93 8 5 6 5 3 31 8 2 6 4 3 50 7 6 6 0 3 87...

Page 19: ...ns Corresponding refrigerant piping length 7 5m Level difference 0m 6 Air flow rate and BF are tabulated below Outdoor Indoor Outdoor temperature CDB EWB C EDB C 20 25 32 35 40 46 TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 125 12 0 18 0 11 4 10 7 3 60 11 1 10 4 3 79 10 3 9 9 4 18 10 0 9 8 4 47 9 5 9 6 4 96 8 8 9 1 5 44 14 0 20 0 12 1 10 7 3 66 11 7 10 4 3 86 11 0 9 9 4 25 10 7 9 8...

Page 20: ...08 24 0 32 0 9 4 1 99 9 1 2 16 8 6 2 42 8 4 2 59 8 0 2 85 7 4 3 11 9 4 1 99 9 1 2 16 8 6 2 42 8 4 2 59 8 0 2 85 7 4 3 11 100 12 0 18 0 8 4 2 53 8 3 2 80 8 1 3 16 7 8 3 34 7 5 3 70 6 8 4 15 8 4 2 53 8 3 2 80 8 1 3 16 7 8 3 34 7 5 3 70 6 8 4 15 14 0 20 0 8 9 2 57 8 8 2 85 8 7 3 22 8 4 3 40 7 8 3 77 7 4 4 23 8 9 2 57 8 8 2 85 8 7 3 22 8 4 3 40 7 8 3 77 7 4 4 23 16 0 22 0 10 1 2 62 9 8 2 90 9 1 3 27 8...

Page 21: ...ing terminal M5 in switch box 5 Refrigerant piping intake 6 Power supply wiring intake knock out hole ø34 7 Control wiring intake knock out hole ø27 8 Drain outlet RR100B7 3TW26394 1 hole for anchor bolt 4 M12 LEGEND 1 Gas pipe connection ø15 9 flare 2 Liquid pipe connection ø9 5 flare 3 Service port in the unit 4 Grounding terminal M5 in switch box 5 Refrigerant piping intake 6 Power supply wirin...

Page 22: ...ing RR125B7 3TW26414 1 hole for anchor bolt 4 M12 LEGEND 1 Gas pipe connection ø15 9 flare 2 Liquid pipe connection ø9 5 flare 3 Service port in the unit 4 Grounding terminal M5 in switch box 5 Refrigerant piping intake 6 Power supply wiring intake knock out hole ø34 7 Control wiring intake knock out hole ø27 8 Drain outlet ...

Page 23: ...27 5 Split Sky Air Outdoor Units 21 Outdoor Units R 410A RR B7 5 Dimensional drawing centre of gravity 5 2 Centre of gravity R Q R 71B7 3TW26329 5B R Q R 100B7 3TW26349 5B ...

Page 24: ... Outdoor Units R 410A RR B7 Split Sky Air Outdoor Units 22 27 5 5 Dimensional drawing centre of gravity 5 2 Centre of gravity R Q R 125B7 3TW26369 5B ...

Page 25: ...connection Flange connection Pinched pipe Spinned pipe Filter Heat exchanger Indoor unit RR71 125B7 twin 3TW26375 2 Heat exchanger Electronic expansion valve Heat exchanger Filter Filter Field piping Field piping Indoor unit Indoor unit Field piping Field piping Branch pipe option Stop valve with service port 5 16 flare Field piping ø9 5 C 1220T 0 Field piping ø15 9 C 1220T 0 Service port 5 16 Hea...

Page 26: ...ort 5 16 flare Field piping ø9 5 C 1220T 0 Field piping ø15 9 C 1220T 0 Service port 5 16 Heat exchanger Muffler High pressure switch Low pressure switch Filter Filter Receiver Solenoid valve Strainer Compressor Outdoor unit NOTE 1 The pipes between the branch and the indoor units should have the same size as the indoor connections Check valve Flexible connection Flare connection Screw connection ...

Page 27: ...erminal BLK black BLU blue ORG orange RED red WHT white YLW yellow Live Neutral Connector Protective earth screw Terminal outdoor 71 100 class RR71 100B7W1B 2TW26386 1B LEGEND A1P Printed circuit board BS1 Push button switch forced defrost pump down C1 Capacitor M1F DS1 Dip switch E1HC Crankcase heater F1U F2U Fuse T6 3 250V HAP Light emitting diode service monitor green K1M Magnetic contactor M1C...

Page 28: ...kage breaker 30 mA Q1M Thermo switch M1F Q1RP Phase reverse circuit R1T Thermistor Air R2T Thermistor Coil R3T Thermistor Discharge pipe RC Signal receiver circuit S1PH Pressure switch high S1PL Pressure switch low SD Safety devices input T1A Current transformer TC Signal transmission circuit X1M X2M Terminal strip Y1E Expansion valve electronic Y1S 4 way valve Y2S Solenoid valve CT Current transf...

Page 29: ... Air Outdoor Units 27 Outdoor Units R 410A RR B7 7 Wiring diagram 7 2 External connection diagram R Q R 71 125B7 4TW26329 7 I Pair II Twin III Triple M Master S Slave 1 Earth leak detector 2 Fuse 3 Remote controller ...

Page 30: ...ctave band center frequency Hz Sound operation level dB Measuring location discharge side NOTES 1 Data is valid at free field condition 2 Data is valid at nominal operation condition 3 dBA A weighted sound operation level A scale according to IEC 4 Reference acoustic pressure 0dB 20μPa 5 Curve for RQ100B7 and RR100B7 in cooling mode RR RQ125B7 Cooling 3TW26367 1 Octave band center frequency Hz Sou...

Page 31: ...ling 3TW26347 3 Octave band center frequency Hz Sound operation level dB NOTE 1 Data is valid at free field condition 2 Data is valid at nominal operation condition 3 dBA A weighted sound operation level A scale according to IEC 4 Reference acoustic pressure 0dB 20μPa 5 Curve for RQ100B7 and RR100B7 in cooling mode RR RQ125B7 Cooling 3TW26367 3 Octave band center frequency Hz Sound operation level...

Page 32: ...00B7W1B RR125B7W1B 2 Depending on operation and installation conditions the indoor unit can change over to freeze up operation indoor de icing 3 To reduce the freeze up operation indoor de icing frequency it is recommended to install the outdoor unit in a location not exposed to wind Outdoor temp CDB Indoor temp CWB COOLING Outdoor temp CDB Outdoor temp CDB ...

Reviews: