4
|
Components
Service manual
135
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
4.12.2 Class 42~71 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Measure the voltage between the black and white wires.
Result:
The measured voltage MUST be 230 V AC.
a
b
a
Black wire
b
White wire
Is the measured voltage on the PCB
correct?
Action
Yes
Return to
135] of the PCB and
continue with the next procedure.
No
Continue with the next step.
3
Check the power supply to the unit, see
205].
Does the unit receive power?
Action
Yes
Replace the main PCB, see
140].
No
Adjust the power supply to the unit, see
To check the HAP LED of the main PCB
Prerequisite:
First check the power supply to the main PCB, see
135].
1
Locate the HAP LED on the main PCB.