3
|
Components
Service manual
91
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
To remove the humidity sensor wiring harness
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Disconnect the wiring harness from the humidity sensor (PCB).
2
Disconnect the wiring harness connector from the indoor unit main PCB.
3
Cut all tie straps (if any) that fix the wiring harness.
4
Route the wiring harness out of the harness retainers and remove the
humidity sensor wiring harness.
5
To install the humidity sensor wiring harness, see
To install the humidity sensor wiring harness
1
Connect the wiring harness connector to the indoor unit main PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
2
Route the wiring harness through the appropriate harness retainers towards
the humidity sensor (PCB).
3
Connect the wiring harness to the humidity sensor (PCB).
4
Fix the wiring harness using new tie straps (if needed).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.8 Indoor unit fan motor
3.8.1 Wall mounted indoor units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the DC fan motor assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Check the fan for damage, deformations and cracks. Replace the fan as
needed.
2
Check that the fan is correctly installed on the DC fan motor. Correct as
needed.