9.0 TROUBLE SHOOTING
PROBLEM
POSSIBLE CAUSE
ACTION
LACK OF COOLING EFECT
1. Faulty compressor or lack of
compression.
1. Check discharge pressure for
compression. Inspect compressor
and replace if necessary.
2. Temperature of air entering
evaporator too high.
2. Reduce load to design KW
value.
3. Fouled condenser and/or
evaporator tube surface.
3. Inspect surface and clean.
4. Low refrigerant charge.
4. Repair refrigerant leak, add
refrigerant.
5. Thermal expansion valve out of
adjustment or erratic.
5. Adjust superheat or replace
power element.
6. Improper air flow through
evaporator.
6. Determine flow and adjust
correctly belt tension.
7. Room thermostat not operating
properly.
7. Inspect thermostat and replace
if necessary.
TRIPPING OF
COMPRESSOR(S)
A. DUE TO LOW PRESSURE CUT OUT
1. Reduced air flow through
evaporator.
1. Inspect surface & clean, check
evaporator fan drive
2 Low refrigerant charge.
2. Repair refrigerant leak, add
refrigerant.
3. Broken expansion valve.
3. Replace expansion valve.
4. Restricted refrigerant line.
4. Determine the cause of
restriction and repair.
5. Faulty low pressure cut-out.
5. Replace.
B. DUE TO HIGH PRESSURE CUT-OUT
1. Air in refrigeration system.
1. Re-evacuate refrigeration
system and charge with new
refrigerant.
2. Excess refrigerant charge.
2. Bleed off excess refrigerant.
3. Faulty high-pressure cut-out.
5. Replace.
C. DUE TO COMPRESSOR OVERLOAD TRIPPING
1. Compressor over-current, under
voltage or single phasing.
1. Check electrical supply,
contactors, wiring, and rectify
fault.
2. Excessive discharge pressure.
2. See section B above.
3. Compressor over-heating due to
low refrigerant.
3. Check refrigerant charge (fix
leak), top up refrigerant if
necessary.
4. Compressor motor has a
winding shorted.
4. Replace compressor.
5. Liquid refrigerant in
compressor causing valve plate
damage and lack of compression.
5. Check that crankcase heater is
functioning properly.
6. Defective overload protector.
6. Replace protector.
EXCESSIVE BELT
"SCREAM" WHEN FAN(S)
START UP
1. Slipping belts.
1a. Apply belt dressing/belt
tensioning.
1b. Adjust belt tension correctly.
Summary of Contents for O-WCP16-SEP21-2
Page 13: ...Issue O WCP16 SEP21 2 Page 9 5 1 UNIT DIMENSION 5 1 1 Outline UCQ60A D L...
Page 14: ...Issue O WCP16 SEP21 2 Page 10 5 1 2 Outline UCQ90A D L...
Page 15: ...Issue O WCP16 SEP21 2 Page 11 5 1 3 Outline UCQ140A D L...
Page 16: ...Issue O WCP16 SEP21 2 Page 12 5 1 4 Outline UCQ180A D L...
Page 17: ...Issue O WCP16 SEP21 2 Page 13 5 1 5 Outline UCQ240A L...
Page 18: ...Issue O WCP16 SEP21 2 Page 14 5 1 6 Outline UCQ280A L...
Page 19: ...Issue O WCP16 SEP21 2 Page 15 5 1 7 Outline UCQ320A L...
Page 20: ...Issue O WCP16 SEP21 2 Page 16 5 1 8 Outline UCQ360A L...
Page 21: ...Issue O WCP16 SEP21 2 Page 17 5 1 9 Outline UCQ400 520A L...
Page 22: ...Issue O WCP16 SEP21 2 Page 18 5 1 10 Outline UCQ570A L...
Page 23: ...Issue O WCP16 SEP21 2 Page 19 5 1 11 Outline UCQ710A L...
Page 24: ...Issue O WCP16 SEP21 2 Page 20 5 1 12 Outline UCQ870A L...
Page 25: ...Issue O WCP16 SEP21 2 Page 21 5 1 13 Outline UCQ940A L...
Page 29: ...Issue O WCP16 SEP21 2 Page 25 5 6 FAN CURVE 5 6 1 Fan Curve AT 9 9 Model UCQ60 UCQ90...
Page 30: ...Issue O WCP16 SEP21 2 Page 26 5 6 2 Fan Curve AT 15 15 Model UCQ140 UCQ180 UCQ240...
Page 31: ...Issue O WCP16 SEP21 2 Page 27 5 6 3 Fan Curve AT 18 18 Model UCQ280...
Page 32: ...Issue O WCP16 SEP21 2 Page 28 5 6 4 Fan Curve ADH 450 Model UCQ320 UCQ360 UCQ710...
Page 33: ...Issue O WCP16 SEP21 2 Page 29 5 6 5 Fan Curve ADH 500 Model UCQ400 UCQ520 UCQ870 UCQ940...
Page 34: ...Issue O WCP16 SEP21 2 Page 30 5 6 6 Fan Curve ADH 560 Model UCQ570...
Page 58: ...Issue O WCP16 SEP21 2...