Daikin MQFVI5 Installation And Maintenance Manual Download Page 10

IM 1102 • PARALLEL TERMINAL BOX 10 www.DaikinApplied.com

T

roubleshooTIng

Specific Electric Heat Troubleshooting Procedures: 

 WARNING

Electric shock hazard . Can cause personal injury or 

equipment damage . 

This equipment must be properly grounded. Connections and 

service to the MicroTech III Chiller Unit Controller must be 

performed only by personnel knowledgeable in the operation 

of the equipment being controlled.

WARNING: 

On all troubleshooting that requires you to 

work inside the heater wiring casing, disconnect power first! 

Jumpers are used for diagnostic purposes only – remove all 

jumpers prior to returning unit to operation. 

Table 1: Electric Heat Troubleshooting Procedures

Possible Cause

Solution

Power not properly connected to the heate. 

With a voltmeter, check the power wiring terminals to insure the proper voltage is available to the element side of the 

power terminal block or to the field side of the disconnect switch, power fusing, or circuit breakers. If proper voltage is 

not present, check the terminal studs for proper wiring and check the power source for power. 

Disconnect switch, toggle switch, or circuit 

breaker set to OFF

Set switch circuit breakers to the ON position. 

Power fuses are blown or circuit breakers 

have tripped

Replace fuses with the same type and amperage as those provided with the heater, or reset circuit breaker by first 

setting the breaker to the OFF position, and then resetting it to the ON position. With an ammeter, check amperage 

draw on the power lines. For heaters with fusing, amperage draw should not exceed the fuse. For heaters with circuit 

breakers, amperage should not exceed the rated value. If the amperage draw is excessive, check the power supply as 

described above for proper voltage. If the fuse/circuit breaker trips upon application of power, check for a short. If no 

short is present and the power supply wiring/voltage is correct, contact the factory for further assistance. 

Manual reset switch has been tripped

Push manual reset button. Manual reset is usually located in the control cabinet near the bottom of the been tripped. 

element header. 

Air static switch is not engaging

Jumper out the air static switch by connecting the lead attached to the normally open stud, to the normally closed stud. 

If heater operates, the problem may be the air static switch. Disconnect the pneumatic tubing from the pitot tube located 

in the control cabinet. Attach a magnehelic gauge to the pitot tube. Available static pressure at the pitot tube should be 

<= -0.03" S.P. or >= +0.03" S.P. If the available static pressure is in the dead band between these two ranges, the switch 

will not engage and some method must be devised to increase the available static pressure. If sufficient static pressure 

is available, check to insure the pneumatic tube is connected to the correct port of the switch. For negative pressure, 

connect to the low port. For positive pressure, connect to the high port. If the air static switch still fails to operate, contact 

the factory for a replacement switch

Automatic reset switch bad

Allow the duct temperature to cool below 90°F. If the heater does not operate, jumper out the automatic reset switch. If 

the heater now operates, contact the factory for a replacement switch. Manual reset switch Allow the duct temperature to 

cool below 90°F. If the heater does not operate, do the following: 

• On heaters with the manual reset installed in the power wiring, jumper out the manual reset switch. If the heater now 

operates, contact the factory for a replacement switch. 

• On heaters with the manual reset located in the backup contactor circuit, jumper out the manual reset switch. If the 

backup contactor now engages, contact the factory for a replacement switch. If the backup contactor fails to operate, 

the problem is in the backup contactor holding coils. Use an ohmmeter to check the continuity of the holding coils. 

Contact the factory for a replacement of any contactor with faulty holding coils. 

Step controller malfunction

Jumper out each step of the step controller. If contactor engages, the trouble is in the step controller. Refer to the 

literature provided with the step controller for proper power and wiring. If wiring appears to be correct, contact the factory 

for assistance. 

SCR controller malfunction

Refer to the literature provided with the SCR controller for proper power and wiring. If wiring appears to be correct, 

contact the factory for assistance. 

Possible: Nuisance Tripping of Reset Switches 

Insufficient air flow across the heating 

elements 

The minimum allowable air flow across the heating coils is 70 CFM/kW. Unless this minimum air flow is met, the leaving 

air temperature will be greater than the set point of the high temperature limit switches. This will cause nuisance tripping 

of the reset switches. Reset the minimum air flow across the coils to the minimum listed value. If further assistance is 

needed, contact the factory 

Summary of Contents for MQFVI5

Page 1: ...Installation and Maintenance Manual IM 1102 Group Applied Air Systems Part Number IM 1102 Date October 2010 Parallel Fan Powered Variable Air Volume VAV Terminal Box Model MQFVI5 ...

Page 2: ... 4 Connecting Ductwork 6 Minimum Clearance for Access 6 Field Electrical Wiring 6 Fan Powered Air Terminal Units with Electric Heat 6 Fan Powered Air Terminal Units with Hot Water Coils 6 Controls 7 Labeling 7 Flow Sensor 7 Initial Start up Adjustment of Fan Flow Rate 7 Fan Maintenance Procedure 7 Troubleshooting 8 Possible Conditions 8 Investigating Noise Complaints 9 Controls 9 Electric Duct Hea...

Page 3: ... for his or her application The following are trade names or registered trademarks of their respective companies BACnet from the American Society of Heating Refrigerating and Air Conditioning Engineers Inc Windows from Microsoft Corporation Daikin and MicroTech from Daikin Applied Hazardous Information Messages Familiarize yourself with the hazard identification messages used in this manual DANGER...

Page 4: ...e mounted right side up The fan powered unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle of air flow The control side of the terminal is labeled with an arrow indicating UP Unless otherwise noted most analog and digital controls may be installed in any orientation Check with the local Daikin representative for verification CAUTION The equip...

Page 5: ...Installation www DaikinApplied com 5 IM 1102 PARALLEL TERMINAL BOX Figure 1 Hanging straps Figure 2 Trapeze Hangers Figure 3 Optional hanging brackets and hanger rods ...

Page 6: ...ck hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled All field wiring must comply with the local codes and with the National Electrical Code ANSI NFPA 70 2002 When applicable electrical ...

Page 7: ...pped to California 7 Orientation label identifies the proper air flow direction and the top of the unit Flow Sensor Fan Powered Air Terminals are shipped with a factory installed pressure differential flow sensor installed See Figure 4 for the calibration curve Initial Start up Adjustment of Fan Flow Rate WARNING Solid state speed controls cause all electric motors to run hotter and speed reductio...

Page 8: ...ged intake filter if supplied 4 Re adjust the fan speed control 5 Discharge static pressure too high If repair or replacement of blower or motor is required the motor and fan should be removed as an assembly 1 Disconnect power prior to removal 2 Remove the bottom blower access panel 3 Disconnect the two electrical leads from Terminal Connection 1 and 2 on the motor 4 Remove the bottom two lug scre...

Page 9: ...n concerning controls provided by Daikin For controls provided by others contact the local control representative for assistance Electric Duct Heater WARNING Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operati...

Page 10: ...rom the pitot tube located in the control cabinet Attach a magnehelic gauge to the pitot tube Available static pressure at the pitot tube should be 0 03 S P or 0 03 S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient static pressure is available check to ...

Page 11: ...Troubleshooting www DaikinApplied com 11 IM 1102 PARALLEL TERMINAL BOX Figure 4 MI Flow Sensor Calibration Chart ...

Page 12: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Reviews: