www.DaikinApplied.com 43
OM 752-4
Configuration Parameter Name
Abr.
Notes
Default
LUI
Menu
item
1
Economizer IA/OA Enthalpy Differential
EED 1
.3 btu/lb (3 kJ/kg)
e6
External BI-3 Configuration
0 = Ventilation Lockout, 1 = Exhaust Interlock
0
B3
Filter Alarm Enable
0 = disable, 1 = enable
0
CE
Filter Change Hours Setpoint
fan run hours between filter change alarms
700 hrs
ce
Primary Cool Proportional Band
18°F (10°C)
Primary Cool Integral Time
180 sec
Primary Heat Proportional Band
54°F (30°C)
Primary Heat Integral Time
300 sec
Discharge Air Temp Proportional Band
3.996°F (2.22°C)
Discharge Air Temp Integral Time
300 sec
CO2 Proportional Band
100 PPM
CO2 Integral Time
600 sec
Ventilation Cooling Low Limit Setpoint
VCLL
discharge air low limit during ventilation or economizer cooling
54°F (12°C)
d2
Discharge Air High Limit
DAHL
125°F (51.7°C)
Space Fan Off Delay
4 min
Fan Cycling Configuration
space fan operation during occupied, standby and bypass occupancy modes: 2 =
continuous, 3 = cycle
2
cf
Space Fan Speed Changes Per Hour
example: 6/60min = 10 min (maximum of 1 fan speed change every 10 min when
fan in auto)
6
Space Fan Run Time Reset
reset total run time: 1 = reset (you must return the variable back to 0 after reset)
0
Space Humidity Sensor Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is
ordered with optional humidity sensor)
0
Outdoor Humidity Sensor Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is
ordered with optional humidity sensor)
0
OAD Stroke Time
90 sec
Application Name and Version Label
1. Indicates parameters accessible through the keypad/display.
2. Requires optional equipment.
d
IaGnostICs
and
s
erVICe