IM 972-2 • MAVERICK I ROOFTOP SYSTEMS 14 www.DaikinApplied.com
Electrical Installation
Electrical Installation
Wiring
Power Supply
DANGER
Power supply to the unit must be disconnected before making field
connections. To avoid electrical shock, personal injury or death, be sure to
rigorously adhere to field wiring procedures regarding proper lockout and
tagout of components.
1. All wiring should be made in accordance with the
company to determine the availability of sufficient power
to operate the unit. Check the voltage at power supply to
make sure it corresponds to the unit’s RATED VOLTAGE
REQUIREMENT. Install a branch circuit disconnect near
the rooftop, in accordance with the N.E.C., C.E.C. or
local codes.
2. It is important that proper electrical power is available at
the unit. Voltage should not vary more than 10% from
that stamped on the unit nameplate. On three phase
units, phases must be balanced within 3%.
3. For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of
using the circuit
ampacity found on the unit rating plate. Use the smallest
wire size allowable from the unit disconnect to the unit.
Wire size based on 75°C rated wire insulation for 1%
voltage drop.
4. For more than 3 conductors in a raceway or cable, see
the N.E.C. (C.E.C. in Canada) for derating the ampacity
of each conductor.
5. For through-the-base wiring entry, reference
. All fittings and conduit are field-supplied for this
conduit size.
IMPORTANT:
This unit is approved for use with copper
conductors only connected to unit contactor. Warranty will be
voided if aluminum wire is connected to unit contactor.
Figure 13: Recommended Branch Circuit Disconnect
Location
Figure 14: Base Entry Locations (Cooling Only)
Figure 15: Base Entry Locations (Gas Heat)
DISCONNECT
RUN THERMOSTAT
WIRING IN THIS
CHASE TO
CONTROL
BOARD
(2) CAP PLUGS
BASE
CONTROL
ENTRY
BASE
POWER
ENTRY
POWER WIRES
FROM DISCONNECT
TO TERMINAL BLOCK
WASHERS
CONTROL VOLTAGE
KNOCKOUT
WIRE FROM
ZONE THERMOSTAT
STRAIGHT CONDUIT
FITTING
CONDUIT FROM
ZONE THERMOSTAT
CONDUIT FROM
POWER SUPPLY
SIZED PER CHART
STRAIGHT CONDUIT
FITTING SIZED
PER CHART
WIRE SIZE FROM
MIN. CIRCUIT AMPACITY
CUT HOLE
SIZED PER CHART
OR USE KNOCK OUT
GAS LINE
EXTERNAL MANUAL GAS
SHUT-OFF VALVE
RUN THERMOSTAT
WIRING IN THIS
CHASE TO CONTROL
BOARD