IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS
22 www.DaikinApplied.com
I
nsTallaTIon
RapidRestore
®
and RideThrough
®
WME chillers have the capability for chillers to restart and
reach full load operation quickly in the event of a power loss.
Table 9: RapidRestore
®
and RideThrough
®
Times
Standard
Compressor
Re-Start
RapidRestore
®
Compressor
Re-Start
Fast Loading
to 80% Load
RideThrough
®
60 sec
20 sec
after power
failure*
75 sec**
5 sec***
* Requires customer supplied Uninterruptible Power Supply (UPS) to the WME
control panel.
** After compressor re-start time
*** Time is based on unit operating at AHRI conditions.
Figure 23: RapidRestore
®
Wiring Diagram
Power Panel Short Circuit Current
Ratings
Available short circuit current ratings (SCCR) are shown in
Table 10: Short Circuit Current Ratings
Motor
Code
Voltage
Standard
Panel
SCCR
Optional
High
SCCR
Optional
Ultra High
SCCR
M6, M7, 66
and 77
380V - 480V
35 kA* / 50 kA
65 kA
100 kA
575V
25 kA
35 kA / 50 kA
N/A
68 and 79
380V - 480V
N/A
65 kA
100 kA
575V
25 kA
35 kA / 50 kA
N/A
M8, M9, 88
and 99
380V - 480V
50 kA
65 kA
100 kA
575V
25 kA
35 kA
65 kA
NOTE:
* 600 amp circuit breaker frame size has a 35 kA
SCCR rating. 800 amp circuit breaker frame size has
a 50 kA SCCR rating.
RapidRestore
®
–
Quickly restores cooling capacity when
power is restored after a power failure.
•
Compressor Re-Start –
Amount of time required for
the chiller to re-start.
•
Fast Loading –
Amount of time required for the
chiller to reach a certain load condition.
RideThrough
®
–
The ability to maintain operation during
a momentary power loss event. When RideThrough
®
is enabled and a power loss occurs, the compressor
motor maintains rotation and the VFD catches and
re-synchronizes with the spinning rotor. This permits
the chiller to return to its pre-power loss capacity within
seconds of power being restored.
DAIKIN APPLIED AMERICAS
CHANGES
DRN
REV. DATE
REVISION
PAGE
ECO
THE CONTENTS OF THIS MATERIAL ARE CONFIDENTIAL AND PROPRIETARY TO
DAIKIN APPLIED. ANY UNAUTHORIZED USE, REPRODUCTION, DISCLOSURE
OR TRANSFER IS STRICTLY PROHIBITED. IF FURNISHED WITH A PROPOSAL,
RECIPIENT MAY USE THIS MATERIAL SOLELY TO EVALUATE SUCH PROPOSAL.
IF FURNISHED TO AN EXISTING OR POTENTIAL VENDOR, THIS MATERIAL MAY
BE USED SOLELY IN PREPARATION OF PROPOSAL OR PERFORMANCE OF WORK
FOR DAIKIN APPLIED.
PART NUMBER
REV
1
2
12
3
4
5
6
7
8
9
10
11
02
336078102
0A
6/3/2019
WRH
0A
C000910536
ADDED LOCAL NOTES OF APPLICABILITY TO RAPID RESTORE AND
WME-C UNIT BOX SCH
STANDARD CONFIGURATION ON PAGE 02 AND LABELS.
RAPID RESTORE OPTION
WME DUAL POWER
20 32
RPS
POWER SOURCE SUPPLIED BY OTHERS
100-240VAC; 50-60Hz; MIN UPS OUTPUT 240VA; 2A
RM
WME SINGLE RR
PE
BLK
BLK
GRN
PE
CMPR1
PE
CMPR2
GRN
GRN
PE
PE
CMPR1
SEE DWG 336078103
SCHEM, COMPRESSOR CONTROLLER
BLK
BLK
BLK
BLK
RR
STANDARD 24V POWER
WME DUAL PWR
WME SINGLE PWR
BL
K
BL
K
G
RN
CMPR1
PE
PE
20 32
32
RM
G
RN
CMPR2
CMPR1
G
RN
PE
SEE DWG 336078103
BL
K
BL
K
BL
K
BL
K
PE
SCHEM, COMPRESSOR CONTROLLER
20
24N-21
PE
120
N
U
P
W
R
1-
#
7
U
P
W
R
1-
#
2
U
P
W
R
2-
#
1
U
P
W
R
1-
#
1
U
P
W
R
1-
#
1
U
P
W
R
1-
#
1
U
P
W
R
1-
#
2
U
P
W
R
1-
#
7
2
4
N
-6
24-
22
U
P
W
R
2-
#
7
U
P
W
R
1-
#
7
U
P
W
R
1-
#
1
U
P
W
R
2-
#
2
U
P
W
R
2-
#
1
U
P
W
R
1-
#
2
24-41
120
V
24-40
24N-20
U
P
W
R
1-
#
2
U
P
W
R
1-
#
7
U
P
W
R
2-
#
7
U
P
W
R
2-
#
2
24-
22
2
4
N
-6
SECT 2
STANDARD OPTION APPLICABLE TO THE FOLLOWING PART NUMBERS:
33565990X; 33565991X; AND 33565992X
RAPID RESTORE OPTION APPLICABLE TO THE FOLLOWING PART
NUMBERS: 33865993X
DRAWING 3360781020A01