3 Dehumidification mode
The unit have dehumidification control by a reheat coil, which is under the evaporator coil. To execute
dehumidification, controller setting is required. (Refer to Page 3-12)
In dehumidification, the Reheat Solenoid Valve (RSV) opens to flow high pressure and high temperature
refrigerant to reheat coil. The "DEHUMID" LED lamp will light up.
The following setting can be made:
1) Dehumidification range: 60–95%RH