2.4 OPERATION MODES AND CONTROL
The relationship between the operation mode and setting temperature is as follows.
Operation mode
Setting temperature
Control sensor
Operation description
Frozen mode
–10.1˚C to –30.0˚C
Return air
Compressor ON/OFF control
(+13.8˚F to –22.0˚F)
temperature sensor
A27A (DECOS
3
c)
–3.0˚C to –10.0˚C
Capacity control operation
Partial frozen
(+26.6˚F to +14.0˚F)
Return air
with suction modulating valve
mode
A27B (DECOS
3
d)
temperature sensor
and hot-gas bypass control
–3.1˚C to –10.0˚C
(+26.4˚F to +14.0˚F)
A27A (DECOS
3
c)
–30.0˚C to –2.9˚C
Capacity control operation
Chilled mode
(+86.0˚F to +26.8˚F)
Supply air
with suction modulating valve
A27B (DECOS
3
d)
temperature sensor
and hot-gas bypass control
–30.0˚C to –3.0˚C
(+86.0˚F to +26.6˚F)
Defrosting mode
–
–
Hot-gas defrosting with
refrigerant metering control
Summary of Contents for LXE10E-A27A