14 Electrical installation
Installation and operation manual
28
LRYELRNUN5A7Y1
CO
₂
Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
(a)
If the total transmission wiring exceeds these limits,
communication errors might occur.
Remote switches
See details in:
▪
"14.6.1 Low voltage wiring – Outdoor unit"
▪
"14.7.1 Low voltage wiring – Capacity up unit"
Output signals
See details in:
▪
"14.6.2 High voltage wiring – Outdoor unit"
▪
"14.7.2 High voltage wiring – Capacity up unit"
14.6
Connections to the outdoor unit
NOTICE
▪ Be sure to keep the power line and transmission line
apart from each other (≥50 mm). Transmission wiring
and power supply wiring may cross, but may not run
parallel.
▪ Transmission wiring and power supply wiring may not
touch internal piping in order to avoid wire damage due
to high temperature piping.
▪ Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
Low voltage wiring
▪ DIII transmission wiring
▪ Remote switches (operation, low
noise)
High voltage wiring
▪ Output signals (caution, warning,
run, operation)
▪ Power supply (including earth)
14.6.1
Low voltage wiring – Outdoor unit
Connections/routing/fixing
b
F2
F1
F1
X1M (A1P)
c
a
F2 Q1 Q2
TO
MULTI UNIT
TO
OUT/D UNIT
TO
IN/D UNIT
d e
2
1
3
X5M
a/b/c
d/e
X1M (A1P)
X5M
1
2
X1M (A1P)
DIII transmission wiring:
a: To capacity up unit
b: To indoor units (air conditioning)
c: To communication box
X5M
Remote switches:
d: Remote operation switch
e: Remote low noise switch
X1M (A1P)
X5M
1
2
f
f
Wiring intake (knockout hole) for low voltage. See
"14.3 Guidelines when knocking out knockout
holes"
27].
Details – DIII transmission wiring
"14.5 Specifications of standard wiring components"
Details – Remote operation switch
NOTICE
Remote operation switch
. The unit is factory-equipped
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn ON/OFF
operation of the outdoor unit, a remote operation switch is
required. Use a voltage-free contact for microcurrent
(≤1 mA, 12 V DC). Connect to X5M/1+2, and set to
"Remote".
REMOTE
OFF ON
S1S
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation
switch
Wiring remote operation switch:
Wiring
Sheathed cable (2 wires)
Vinyl cords
0.75~1.25 mm²
Maximum wiring length
130 m
Details – Remote low noise switch
NOTICE
Low noise switch
. If you want to remotely turn ON/OFF
low noise operation, you must install a low noise switch.
Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC).