Operation manual

7

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74303-1C – 2016.02

10-2-2

Selection, installation, work failures specified 
below and other failures

Note: Asterisk-marked items show concrete examples.

1. Model selection failures

A model not suitable for storage applications is selected.
* The cooling of products not reaching the target storage 
temperatures.

Cooling overloading or underloading judged by our dealer.
* The frequency of stoppage is 6 or more times per hour or the 
set cooling temperature is not attained.

2. Installation failure (installation and environmental problems)

The unit is not installed on a stable horizontal plane.
* The unit is not fixed securely.

The environmental conditions of the place of installation differ 
from normal atmospheric conditions.
* Briny air environment, shore side, oil mist environment, 
kitchen exhaust side, other corrosive gas and adhesive mist 
environment.

The place of installation had poor ventilation and heat 
dissipation.
* The machine took in exhausted air again.

3. Work failure

The interior of the piping was not vacuum dried sufficiently.
* The clogging of the thin areas of the piping caused by icing.

The interior of the piping was not sufficiently airtight.
* Leakage of refrigerant gas.

The interior of the piping was contaminated with foreign 
substance.
* The clogging of the thin areas of the piping.

The unit was adversely affected by on-site modification work.
* The use of the unit beyond the operating temperature range as a 
result of on-site modification.

An accident resulted from the improper handling of the unit 
under installation work.
* The loosening or wobbling of the outer panel or broken or bent 
damage to the piping.

4. Operational failure

Temperature settings for stored objects were wrong.
* The storage of vegetables at temperatures below 0°C.

The periodical maintenance of the unit was neglected.
* The clogging of the air heat exchanger, rust generation from 
each part, gas leakage, and icing of the indoor unit (showcase 
and unit cooler).

5. Others

Improvements recommended by our dealer in advance were 
not accomplished.
* The simultaneous starting and stopping of a number of units.

Accidents were caused by natural disaster or fire.
* Damage to electrical parts caused by lightning.

There were other installation and operational problems beyond 
common sense.
* The use of the unit without heat insulation work on the piping.

Work was conducted without keeping the following showcase 
restrictions.
<Showcase restrictions>
· The installation of the thermostatic expansion valve and 

liquid supply solenoid valve (both of which are for R410A) on 
a showcase basis.

 

Thermal insulation of feeler tube of thermostatic expansion 
valve must be thermal insulated.

· Install showcases on the same floor if the showcases are 

connected to a single outdoor unit.

· Make sure that the outlet of piping used for the heat 

exchanger is located downward (as shown on the following 
figure).

11.

Inlet 
(upper side)

Outlet 
(lower side)

Heat exchanger

4PWEN74303-1C.book  Page 7  Thursday, March 10, 2016  10:59 AM

Summary of Contents for LREQ10B7Y1

Page 1: ...OPERATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Page 2: ...l dealer about installation work Doing the work yourself may result in water leakage electric shocks or fire hazards Consult your local dealer regarding modification repair and maintenance of the cond...

Page 3: ...a danger of flammable gas leakage In the event of a gas leakage build up of gas near the condensing unit may result in fire hazards Perform drain piping to ensure perfect drainage Imperfect drainage m...

Page 4: ...6 hours before resuming the operation of the unit Note The power consumption of the unit varies with the operating factors such as the condensing unit model 5 2 Install an alarm if operational errors...

Page 5: ...dealer for the replacement of the power supply fuse Is the power circuit breaker not turned off Turn on the power if the knob of the power circuit breaker is set to the OFF position Do not turn on th...

Page 6: ...e target evaporating temperature set for the protection of the unit Model LREQ5 LREQ6 LREQ8 LREQ10 LREQ12 LREQ15 LREQ20 Power supply 3 phase 50 Hz 380 415 V Refrigerant R410A Operating condition Evapo...

Page 7: ...nt Contact your dealer for discarding the system condensing unit since it is required by law to collect transport and discard the refrigerant in accordance with relevant local and national regulations...

Page 8: ...ion work The use of the unit beyond the operating temperature range as a result of on site modification An accident resulted from the improper handling of the unit under installation work The loosenin...

Page 9: ...4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Page 10: ...4PWEN74303 1C book Page 2 Thursday March 10 2016 10 59 AM...

Page 11: ...4PWEN74303 1C book Page 3 Thursday March 10 2016 10 59 AM...

Page 12: ...4PW74303 1C 2016 02 Copyright 2012 Daikin 4PW74303 1 C 0000000L 4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Reviews: