IOM 1062
Direct Drive Fluid Coolers
25
Table 13, Jumper Designations, Positions, and Control Settings
Function
Jumper Pins Designation
on Control
Setting
Jumper
Position*
Factory Default Setting
(and Jumper Position)
Cooling
Removed
Operating Mode
Cooling/Heating
JUMP1
(Top Pair of Pins on Block
P4)
Heating
Installed
Cooling
(Removed position)
At Cut-in
Removed
Setpoint
JUMP2
(Bottom Pair of Pins on
Block P4)
At Cut-out
Installed
Cut-in
(Removed Position)
Locked
Removed
Keypad Lock
P5-Keypad Unlock
Unlocked
Installed
Unlocked
(Installed Position)
*
IMPORTANT
: The keypad cannot be unlocked without a jumper. Do not discard any
jumpers in case they are required in the future. To position a jumper in the Removed
position, place the jumper on only one pin. (Saving the jumper in case it is required in the
future.)
Changing Temperature Units
The A419 control is set at the factory to display in Fahrenheit temperature units.
To convert to Celsius units, press the Up and Down buttons
simultaneously. Press them again to return to Fahrenheit units.
Note
: Make sure the Keypad Lock jumper is in the unlocked (installed) position before
adjusting the control. Verify that the control is displaying the desired temperature units
before setting the setpoint.
Setting the Setpoint
To view and adjust the setpoint, follow these steps:
1. Press and hold the Menu button until the display changes to flashing
SP. This will take about 2 seconds.
Note
: If no entries are made for 30 seconds, the control reverts to the temperature display.
2. Press the Menu button again. The current setpoint is displayed.
3. Press the Up or Down button to adjust the setpoint temperature.
4. Press the Menu button to save. The display then returns to the sensor
temperature
.
Note
: If the Menu button is not pressed after changing the setpoint, the control reverts to
the setpoint value previously programmed into the A419 control.