background image

IM 986-2 / Page 17 of 48

Before furring-in units, hydrostatically test the risers and 

unit connection joints in accordance with local building 

codes, to make sure they are leak-proof.

Note: Perform "Cleaning and Flushing Water 
System" Procedure Below.

When furring-in units make sure that no screws or nails 

penetrate the unit cabinet. 

8.  Layout the stud wall floor plates and frame-in 

unit referencing “Typical Framing & Discharge 
Arrangements” on page 13 and “Critical Dimensions” 
on page 14 and table 1 .

Note: Before cutting and hanging drywall, remove 
the appropriate discharge air opening knockout. See 
Table 2). Protect unit from construction debris with a 
protective cover.

Cleaning and Flushing Water 
System

Prior to first operation of any unit, the water circulating 

system must be cleaned and flushed of all construction dirt 

and debris or damage will occur.

1.  Prior to first operation of any unit, the water 

circulating system must be cleaned and flushed of all 

construction dirt and debris .

 
 

If the units are equipped with water shutoff valves, 
either electric or pressure operated, the supply and 
return runouts must be connected together at each 
unit location . This will prevent the introduction of 
dirt into the unit (Figure 26) .

     CAUTION

Note: Be sure that each riser stub-out (supply & 
return) are centered within the riser knockout in 
the cabinet (Figure 25). If there is a void between 
the stub-out and the stub-out seal on the cabinet 
interior, this indicates that the stub-out is not properly 
centered within the knockout.

Figure 25:  Center the Riser Stub-Outs in the Knockouts and 
within Seals on the Cabinet Interior 

5 .  Anchor risers to the building structure to prevent 

vertical riser movement greater than, plus or minus 
one inch to allow for riser expansion or contraction .

6 .  Solder all supply and return riser connections to 

units above and/or below .

7 .  Remove riser ties used to secure the risers to the 

cabinet during shipping .

Riser Knockouts

Stub-Out Connections with 

Valves Centered within 

Knockouts and Seals

Stub-Outs 

Seals

Cabinet 
Interior

Knockouts 
on Cabinet 
Exterior

CAUTION

WARNING

The unit is not designed to support the weight of the risers.

Anchor them securely to the building structure.

     CAUTION

  

 

 

Discharge Openings

 

 

Unit Size

 

Single 

Double 

 

Triple 

Single-Top Opening

  

W H  W H  W H  W H

 

009–012

 

14" 

16" 

14" 

8" 

NR 

NR 

12" 

12"

 

015–018

 

14" 

16" 

14" 

8" 

14"

 

8" 

12" 

12"

  021–024

 

NR 

NR 

18" 

14" 

18" 

10" 

18" 

18"

 

030–036

 

NR 

NR

 

18" 

14"

 

18" 

10" 

18" 

18

Table 2:  Discharge Knockout Openings

NR =

 

Not Recommended

Summary of Contents for IM 986-2 VHC

Page 1: ...k Water Source Heat Pumps Model VHC Vertical Stack Chassis Model VHF Vertical Stack Cabinet Unit Sizes 009 036 R 410A Refrigerant Group WSHP Part Number 669646403 Date May 2012 IM 986 2 2012 McQuay In...

Page 2: ...Page 2 of 48 IM 986 2...

Page 3: ...stalling the Discharge Air Diffuser 25 Twin Units Installation 26 Controls 27 34 MicroTech III Unit Controller 27 Remote Reset Feature 27 MicroTech III Controller Terminal Locations Descriptions 28 29...

Page 4: ...Side RYY Single Supply Outlet Right Side FYY Single Supply Outlet Front Side BYY Single Back Side Supply Outlet TYY Single Top Supply Outlet LFY Double Supply Left Side and Front Side LRY Double Suppl...

Page 5: ...w E Coated Air Coil EYC IAQ Cellular w E Coated Air Coil AMC Standard w Comp Blanket and Coated Air Coil EMC IAQ w Comp Blanket and Coated Air Coil Motorized 2 Way Isolation Valve C 2 Way Motorized 1...

Page 6: ...evidence of rough handling immediately open the cartons to check for concealed damage If any damage is found notify the carrier within 48 hours to establish your claim and request their inspection and...

Page 7: ...r with local codes and regulations and experienced with this type of equipment WARNING The installer must determine and follow all applicable codes and regulations This equipment presents hazards of e...

Page 8: ...screws on the back of the unit as shown in Figure 4 Note Retain all screws for later use to reassemble unit in reverse order as described in steps 1 7 Number of screws will vary depending on unit size...

Page 9: ...8 11 37 50 88 58 09 2 38 3 125 2 2 6 72 12 4 7 9 3 3 18 18 92 18 07 18 11 37 50 88 58 09 2 38 3 125 2 2 6 72 12 4 7 9 3 3 Cabinet 96 18 07 18 11 37 50 88 58 09 2 38 3 125 2 2 6 72 12 4 7 9 3 3 A R S T...

Page 10: ...50 92 3 09 3 10 3 12 4 50 4 50 96 3 09 3 10 3 12 4 50 4 50 Dimensions Unit Size A B C D E F G J K L M N P Q 80 24 24 04 37 50 88 58 08 2 38 4 54 2 3 6 72 12 13 7 63 3 13 021 036 88 24 24 04 37 50 88 5...

Page 11: ...nt For Optimum Unit Performance and to Help Minimize Noise and Vibration Adhere to the Critical Dimensions for locations of framing and distances to the cabinet Install a 1 4 thick vibration isolation...

Page 12: ...Side Discharge Figure 14 Side Top Discharge See Notice on page 11 Figure 15 Double Side Top Discharge See Notice on page 11 Figure 16 Top Discharge See Notice on page 11 Figure 17 Closed Plenum Field...

Page 13: ...peed 1 021 Speed 2 Speed 1 024 Speed 2 Speed 1 030 Speed 2 Speed 1 036 Speed 2 710 640 710 640 1060 930 1060 930 ECM X13 Motor CFM Sizes 021 036 External Static Pressure Ducted Applications 830 770 83...

Page 14: ...oning the cabinet and connecting to the riser stub outs Figure 20 Vertical Riser Stub Outs Locations to Unit Knockouts 1 Dimension includes approximately 1 4 for vibration isolation pad 2 Dimension E...

Page 15: ...lation and fit up When installed the return air grille gasket must compress and seal completely against the outer edge of the cabinet and around the inner front panel and filter bracket See page 24 In...

Page 16: ...s illustrated in figure 24 Cut away an area of the 1 4 isolation pad at the mounting bracket locations Contractor is responsible for the appropriate fasteners to secure the brackets to the floor as lo...

Page 17: ...each unit location This will prevent the introduction of dirt into the unit Figure 26 CAUTION Note Be sure that each riser stub out supply return are centered within the riser knockout in the cabinet...

Page 18: ...or with the pressure reducing valve open Check vents in sequence to bleed off any trapped air ensuring circulation through all components of the system Power to the heat rejector unit should be off an...

Page 19: ...Locate the electrical power supply wiring from the building and feed wiring through the 1 2 conduit fitting strain relief on the unit as shown in Figure 27 28 following local electrical codes and reg...

Page 20: ...with a 2 way motorized valve The 2 way motorized valve is mounted on the return line of each unit and the Auto Flow Regulator AFR is mounted to the supply line Valve assemblies terminate with either a...

Page 21: ...sharp metal edges To avoid personal injury heavy protective gloves should be used while moving and lifting the unit chassis Note To complete the flexible hose connections to the chassis only partiall...

Page 22: ...sis FPT supply and return pipe connections Using two crescent wrenches one to hold the chassis pipe connection and the second on the adapter fitting tighten the connections 2 Install the chassis by sl...

Page 23: ...o 2 screws at the front of the cover and three 3 located on the underside Figure 38 The wires connected to the manual fan speed switch may be removed for easier access Note There are two methods for i...

Page 24: ...the finished wall Note Shims should be used to make up the space between the studs and the panel frame at the locations of the fasteners on the panel frame 4 Adhere them to the panel frame to keep the...

Page 25: ...Diffuser Foam seal applied to the cabinet face around perimeter of discharge air opening Diffuser flange compresses into the foam seal Double deflection Diffuser Foam seal field furnished installed 3...

Page 26: ...located in the base of the secondary unit Block offs must be installed on the secondary unit before putting it into position Twin Units Installation Twin opposite hand units share a common riser syst...

Page 27: ...ial EEPROM On On On De energized Corrupted Network Offline Off Off Off De enegized Received Table 6 MicroTech III unit controller LED fault outputs 1 Compressor relay compressor terminal is labeled CO...

Page 28: ...r LED Output TB1 2 2 Fan Mode Heat Cool Auto Input TB1 3 3 Setpoint Adjust Input TB1 4 4 Room Temperature Sensor Tenant Override TB1 5 5 DC Signal Common Test 1 R 24 VAC Test 2 W2 Heat Stage 2 Input T...

Page 29: ...f 48 Figure 44 MicroTech III Unit Controller Terminal Locations Location of Configuration Jumpers on the MicroTech III Unit Controller Note A random start delay time between 180 and 240 seconds is gen...

Page 30: ...s Shorted for dual compressor JP2 Hot Gas Open to disable reheat Water Reheat Shorted to enable reheat JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open JP4 shorted for JP4 Heat Type...

Page 31: ...rature Relay status of all vital unit functions Support optional control outputs A set of three status LED s aid in diagnostics by indicating the water source heat pump operating mode and alarm condit...

Page 32: ...nd timed override button wall mounted sensors with LED status timed override button tenant setpoint adjustment buttons password protected field service access to operational data and optional humidity...

Page 33: ...re and generates separate high pressure and low pressure alarms available in software While either alarm is active compressor operation is suspended In a refrigerant low temperature condition an alarm...

Page 34: ...Page 34 of 48 IM 986 2 Figure 48 LonWorks Communication Module Placement on MicroTech III Unit Controller...

Page 35: ...CR Fan Connector Receptacle FSR Fan Speed Relay FSS Fan Speed Switch Optional FS1 Fuse 1 FS2 Fuse 2 HP High Pressure Switch ISO Isolation Valve Optional LED1 LED Annunciator Harness LP Low Pressure Sw...

Page 36: ...an Connector Receptacle FPR Fan Power Relay FSR Fan Speed Relay FSS Fan Speed Switch Optional FS1 Fuse 1 FS2 Fuse 2 HP High Pressure Switch ISO Isolation Valve Optional LED1 LED Annunciator Harness LP...

Page 37: ...or Plug FCR Fan Connector Receptacle FPR Fan Power Relay FSR Fan Speed Relay FSS Fan Speed Switch Optional FS1 Fuse 1 FS2 Fuse 2 HP High Pressure Switch ISO Isolation Valve Optional LED1 LED Annunciat...

Page 38: ...Connector Plug FCR Fan Connector Receptacle FPR Fan Power Relay FSR Fan Speed Relay FSS Fan Speed Switch Optional FS1 Fuse 1 FS2 Fuse 2 HP High Pressure Switch ISO Isolation Valve Optional LED1 LED A...

Page 39: ...MicroTech III unit controller has a fault output signal to an LED on a wall thermostat Table 10 shows in which function the fault output is on sending a signal to the LED Units must be checked for wat...

Page 40: ...e Stage Heat Cool Systems Single Stage Heat Pump Systems Fan Speed Control Large Display With Backlight Selectable Fahrenheit or Celsius Compatible with Gas Oil or Electric SimpleSet Field Programming...

Page 41: ...he Wireless Temperature Control the RCN interfaces with specific HVAC equipment and communicates with its thermostat using unlicensed 900 MHz radio frequency energy Contact your local McQuay Represent...

Page 42: ...r models feature a thermistor 10k and a green LED for unit status Tenant override setpoint adjustment potentiometer thermometer and a communications port are optional features available in any combina...

Page 43: ...cuit board Motorized Isolation Valve Relay The motorized valve kit may be ordered as a field installed accessory Wired as shown in Figure 60 the motorized valve will open on a call for compressor oper...

Page 44: ...eratures All McQuay water source heat pumps are designed for commercial use The units are designed for the cooling mode of operation and fail safe to cooling The reversing valve is energized for the h...

Page 45: ...flow of the refrigerant a hot gas leaving the compressor to the air to refrigerant heat exchanger coil Here the heat is removed by the air passing over the surfac es of the coil and the hot gas conde...

Page 46: ...or lock rotor amp draw Check for defective compressor internal windings with ohm meter Check for proper air flow filter could be dirty Check for low refrigerant charge Check amp draw on blower assembl...

Page 47: ...d thermostat are then connected to the MicroTech III unit controller thermostat inputs and control inputs as needed Any remaining board input s may be operated by additional thermostat outputs or remo...

Page 48: ...ld pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your...

Reviews: