IM 837-2 • MICROTECH II CHILLER UNIT CONTROLLER 14 www.DaikinApplied.com
Network Configuration
Network Configuration
Configure Network Parameters
Once your PC and web browser have been configured and
tested, it is then possible to begin using the BACnet Web
Configuration Interface to set BACnet parameters and other
network options. The remainder of this document is the user
guide for the BACnet Web Configuration Tool. It shows each
HTTP page of the interface and describes the available fields
and addressing parameters. To use the tool:
1. Connect the communication module via the Ethernet
port.
a. Open Internet Explorer or other browser and
Type
http://172.16.5.8/
in the Address box of the
browser.
b. Press Enter to access the communication module.
2.
Click the Go to Configure/Test link at the bottom of the
BACnet Web Configuration Interface home page.
3. Enter the User Name “admin” and Password “fadmin.”
Note that these are the defaults and can be changed.
4. Press OK.
5. Adjust the parameters for your particular network
(
Figure 12
). It may be necessary to navigate to other
pages to find the information you need. For example,
the IP Address can be changed on the System/Network
page.
6. Select the Submit button to set the changes into the
communication module.
NOTE:
Changes do not take effect until the module has been
rebooted.
7. Press the Reboot button after changes have been saved.
8. Wait two minutes and allow the communication module
to complete the reboot. Then navigate to the screen
where you made changes.
9. Verify that the changes were made. You may need
to refresh the screen by pressing the web browser’s
Refresh button or by navigating to View/Refresh at the
top of the page. If the changes are not made, verify that
the LAN Settings are not selected in the browser.
10. Close the browser.
11. Remove the connection to the Ethernet port.
BACnet Properties
Table 4
lists the primary network parameter settings and
Device Object properties supported by the unit controller that
are available via the BACnet Web Configuration Interface’s
BACnet Properties page.
NOTE:
The Device Instance, BACnet IP Address, IP Subnet
Mask, UDP Port, and IP Router Address must be
set during the communication module configuration
process. The
BACnet Web Configuration Interface
must be used for these parameters.
1. Change the items on this page as needed and press the
Save Changes button.
2. If the changes are correct, press the Reboot System
button for the changes take effect (
Figure 13.)
Figure 12:
BACnet Web Configuration Properties Page