background image

IM 1093-1 • SINGLE DUCT VAV TERMINALS 8 

www.DaikinApplied.com

T

roubleshooTIng

Specific Electric Heat Troubleshooting Procedures: 

 WARNING

On  all  troubleshooting  that  requires  you  to  work  inside  the 

heater  wiring  casing,  disconnect  power  first!  Jumpers  are 

used for diagnostic purposes only – remove all jumpers prior 

to returning unit to operation.

Possible Cause

Solution 

Power not properly connected to the heater. 

With a voltmeter, check the power wiring terminals to insure the proper voltage is available to the 

element side of the power terminal block or to the field side of the disconnect switch, power fusing, 

or circuit breakers. If proper voltage is not present, check the terminal studs for proper wiring and 

check the power source for power. 

Disconnect switch, toggle switch, or circuit breaker set to OFF 

Set switch circuit breakers to the ON position. 

Power fuses are blown or circuit breakers have tripped. 

Replace fuses with the same type and amperage as those provided with the heater, or reset circuit 

breaker by first setting the breaker to the OFF position, and then resetting it to the ON position. 

With an ammeter, check amperage draw on the power lines. For heaters with fusing, amperage 

draw should not exceed the fuse. For heaters with circuit breakers, amperage should not exceed 

the rated value. If the amperage draw is excessive, check the power supply as described above 

for proper voltage. If the fuse/circuit breaker trips upon application of power, check for a short. If 

no short is present and the power supply wiring/voltage is correct, contact the factory for further 

assistance. 

Manual reset switch has been tripped. 

Push manual reset button. Manual reset is usually located in the control cabinet near the bottom of 

the been tripped. element header. 

Air static switch is not engaging. 

Jumper out the air static switch by connecting the lead attached to the normally open stud, to the 

normally closed stud. If heater operates, the problem may be the air static switch. Disconnect the 

pneumatic tubing from the pitot tube located in the control cabinet. Attach a magnehelic gauge to 

the pitot tube. Available static pressure at the pitot tube should be <= -0.03" S.P. or >= +0.03" S.P. 

If the available static pressure is in the dead band between these two ranges, the switch will not 

engage and some method must be devised to increase the available static pressure. If sufficient 

static pressure is available, check to insure the pneumatic tube is connected to the correct port of 

the switch. For negative pressure, connect to the low port. For positive pressure, connect to the 

high port. If the air static switch still fails to operate, contact the factory for a replacement switch. 

Automatic reset switch bad. 

Allow the duct temperature to cool below 90°F. If the heater does not operate, jumper out the 

automatic reset switch. If the heater now operates, contact the factory for a replacement switch. 

Manual reset switch Allow the duct temperature to cool below 90°F. If the heater does not operate, 

do the following: 

• On heaters with the manual reset installed in the power wiring, jumper out the manual reset 

switch. If the heater now operates, contact the factory for a replacement switch. 

• On heaters with the manual reset located in the backup contactor circuit, jumper out the manual 

reset switch. If the backup contactor now engages, contact the factory for a replacement switch. 

If the backup contactor fails to operate, the problem is in the backup contactor holding coils. Use 

an ohmmeter to check the continuity of the holding coils. Contact the factory for a replacement of 

any contactor with faulty holding coils. 

Step controller malfunction.

Jumper out each step of the step controller. If contactor engages, the trouble is in the step 

controller. Refer to the literature provided with the step controller for proper power and wiring. If 

wiring appears to be correct, contact the factory for assistance. 

SCR controller malfunction. 

Refer to the literature provided with the SCR controller for proper power and wiring. If wiring 

appears to be correct, contact the factory for assistance. Possible: Nuisance Tripping of Reset 

Switchs 

Insufficient air flow across the heating elements 

The minimum allowable air flow across the heating coils is 70 CFM/kW. Unless this minimum air 

flow is met, the leaving air temperature will be greater than the set point of the high temperature 

limit switches. This will cause nuisance tripping of the reset switches. Reset the minimum air flow 

across the coils to the minimum listed value. If further assistance is needed, contact the factory 

Summary of Contents for IM 1093-1

Page 1: ...Installation and Maintenance Manual IM 1093 1 Group Controls Part Number IM 1093 Date February 2015 Single Duct VAV Terminals...

Page 2: ...on 4 Hanging Installation Requirements 4 Minimum Clearance for Access 5 Connecting Ductwork 5 Field Electrical Wiring 5 MQTHI5 Single Duct Terminal Units with Electric Heat 6 MQTHI5 Single Duct Termin...

Page 3: ...rosoft Corporation Maverick RoofPak and Daikin from Daikin Applied Hazard Identification Messages DANGER Dangers indicate a definate hazardous situation physical or electrical which will result in dea...

Page 4: ...he terminal is critical The pneumatic controls must be mounted right side up The single duct unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle...

Page 5: ...sor is installed it is recommended that the installer provide three to five diameters of straight duct at the terminal inlet The outlet end of the terminal is designed for use with slip and drive duct...

Page 6: ...unication addresses Installing the terminal in a different location than noted on unit label and building plans may result in excessive start up labor Detailed information regarding connection start u...

Page 7: ...e Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while p...

Page 8: ...S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient sta...

Page 9: ...Troubleshooting www DaikinApplied com 9 IM 1093 1 SINGLE DUCT VAV TERMINALS Figure 3 MI Flow Sensor Calibration Chart...

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representativ...

Reviews: