background image

DAIKIN 

ILINQ

 QUICK START GUIDE 

Pressing the ENTER button on a weekday or holiday event screen selects the Event1 Start 

Hour. The UP and DOWN buttons can be used to modify the value. Pressing ENTER accepts 

the new value and selects the Event1 Start Minute. The UP and DOWN buttons can be used to 

modify the value. Pressing ENTER accepts the new value and selects the Event1 AM/PM 

designation. Use the UP or DOWN button to toggle the value and press ENTER to accept. This 

process is repeated for the start and stop time settings for the four events. Additional 

information on time schedule settings is provided in the Daikin 

iLINQ

 User Manual. 

Unit Configuration Settings 

Select the Unit Configuration option from the Main Menu to verify that the unit configurations 

are correct. Many of these settings are set at the factory to match the unit where the controller 

is installed but should be confirmed, and others are determined by site preferences or field-

installed options. Additional information on unit configuration settings is provided in the Daikin 

iLINQ

 User Manual. 

Changing the Control Mode from DDC to TSTAT configures the controller to accept

 

commands from a traditional thermostat instead of using the DDC controller application

 

logic. Follow wiring modification steps outlined in the Daikin 

iLINQ

 User Manual.

Setting Blower Cycling to Yes allows the main blower to be cycled off during occupied

 

hours when there is no need for cooling or heating for applications where continuous

 

fresh air ventilation is not required.

If an economizer option has been installed on the unit, verify that the Economizer

 

setting

 

has been set to Installed or Installed With CO2 as needed.

Setting the Sensor Source selection of a sensor to Network causes the controller to use

 

the sensor value from the LonWorks

®

 or BACnet

®

 communication interface instead of

 

the onboard wiring connections.

Change the Schedule Source from Onboard to Remote if the Remote Start Stop input is

 

to be used for occupancy instead of the defined time schedule. Set to Force Occupied

 

or

 

Force Unoccupied to bypass scheduling.

Summary of Contents for iLINQ

Page 1: ...Daikin iLINQ Quick Start Guide QSG ILINQA ...

Page 2: ...ation Settings 9 Temperature Humidity Setpoints 10 Timers Delays 10 Modify TCP IP Settings 11 View Active Alarms 11 Test and Balance 11 Export Parameters 13 Using the Web Interface 14 PC Configuration 14 Web Access Code 15 Web Interface Access 16 Configure Date Time 17 Configure Time Schedule 18 Unit Configuration Settings 18 Temperature Humidity Setpoints 19 Timers Delays 20 Modify TCP IP Setting...

Page 3: ...guide provides procedures that should be followed for the successful implementation of the Daikin iLINQ controller For more detailed information on any of the features or wiring please refer to the Daikin iLINQ User Manual and the wiring diagram provided with the unit ...

Page 4: ...ntroller check the wire terminations at each terminal block for any loose wires and verify that the 24VAC power wiring at terminal J1 is correct The transformer secondary wired to G0 must be connected to earth ground Using a supply voltage other than specified may cause damage to the controller ...

Page 5: ...d to avoid exposure to direct sunlight other heat sources and drafts from HVAC supply vents Wiring Example No wiring for the push button override feature is required if the jumper in the sensor is left in the factory default Short Sensor position If the jumper is moved to the Separate Input position the O R terminals must be wired to the Remote Start Stop digital input for the push button override...

Page 6: ...blower compartment For best performance the sensor should be relocated to the supply air duct approximately 10 feet downstream of the unit Wiring Example The sensor is wired between U1 on terminal J2 at the controller and ground In some cases controller terminal J2 may be factory wired to a more easily accessible set of terminals in the unit control box In this case the sensor is wired between DAT...

Page 7: ...for Service level access Standard user level access allows for modification of time schedules and common setpoints Service level access allows for unit configuration changes to be made If the user passwords have been modified the new User or Service password must be used instead of the default passwords listed here After successfully logging in the Main Menu is displayed Navigate through the Main ...

Page 8: ... are correct If the date or time need to be updated press ENTER to enter the date time screen and use the UP DOWN and ENTER buttons to update the date and time settings Configure Time Schedule The controller time schedule is used to determine when the unit is considered to be occupied and unoccupied The default time schedule is occupied between 7 30 AM and 5 30 PM Monday through Friday When the sc...

Page 9: ...s or field installed options Additional information on unit configuration settings is provided in the Daikin iLINQ User Manual Changing the Control Mode from DDC to TSTAT configures the controller to accept commands from a traditional thermostat instead of using the DDC controller application logic Follow wiring modification steps outlined in the Daikin iLINQ User Manual Setting Blower Cycling to ...

Page 10: ...ctory settings per site requirements Additional information on temperature and humidity setpoints is provided in the Daikin iLINQ User Manual Timers Delays Select Timers Delays from the Main Menu Scroll through the timers delays and modify factory settings per site requirements Additional information on timers and delays is provided in the Daikin iLINQ User Manual ...

Page 11: ...can be viewed through the onboard display The LED at the ALARM button illuminates red when there is an active alarm View any active alarms by pressing the ALARM button and using the UP and DOWN buttons to scroll if there is more than one active alarm Each alarm provides a brief description of the alarm and up to two related values that were logged at the time that the alarm was generated to help d...

Page 12: ...rvals for the startup or test balance procedures If the unit has been in a Force Mode for longer than 30 minutes without any changes being made to any of the Force Mode settings the unit returns to normal operation If it is determined that economizer minimum positions or blower speed settings need to be adjusted to meet airflow requirements for the site or to match the airflow tables in the unit I...

Page 13: ...From the Main Menu navigate to Settings and press ENTER Navigate to the Export Reset option and press ENTER Under Parameters Import Export select Export select the preferred Memory Type enter a value for the Export File Name and set the Confirm value to Yes Selecting Internal Flash Memory as the Memory Type will save the file to the controller s internal memory Selecting USB will save the file to ...

Page 14: ...ngs have been modified the PC configuration settings needed to connect to the controller will be different than the example given here Connect an Ethernet cable between the PC and the controller using one of the two available controller Ethernet ports Modify the computer s network settings so the IP address is in the range 192 168 1 1 to 192 168 1 254 excluding 192 168 1 16 which is used by the co...

Page 15: ...ers IP address in the address bar of the internet browser Enter the six character case sensitive code into the entry field and press enter or click submit The user will be prompted with an Invalid Code message if the code entered does not match the controller s unique web access code After successfully entering the web access code the set password page of the web interface is displayed Click in th...

Page 16: ... the PC and the controller must be disconnected for the web interface to be functional Using a web browser enter 192 168 1 16 into the address bar and press enter When prompted for a password enter the user or service password After successfully logging in the Main Screen is displayed Navigate through the Web Interface screens using the navigation menu on the left side of the screen ...

Page 17: ...mezone dropdown menu and click the Update Timezone toggle switch Verify that the current date and time are correct If the date or time needs to be updated enter the correct values in the Set Date and Set Time fields and click the Update Date Time toggle switch Alternatively clicking the Sync Date Time toggle switch sets the controller date and time to the same values as the date and time on the co...

Page 18: ...ch the unit where the controller is installed but should be confirmed and others are determined by site preferences or field installed options Additional information on unit configuration settings is provided in the Daikin iLINQ User Manual Changing the Control Mode from DDC to TSTAT configures the controller to accept commands from a traditional thermostat instead of using the DDC controller appl...

Page 19: ...instead of the defined time schedule Set to Force Occupied or Force Unoccupied to bypass scheduling Temperature Humidity Setpoints Select Parameters Temperature Humidity Setpoints from the Main Menu Modify factory setpoints per site requirements See the Daikin iLINQ User Manual supplied with the unit for a detailed description of each setpoint ...

Page 20: ... must be provided by the network administrator Navigate to the Settings Communication screen in the Navigation Menu to view and modify the TCP IP settings Set the DHCP toggle switch to Enabled if the network will automatically assign IP addresses to connected devices If a static IP address is used enter the appropriate IP Address Subnet Mask Default Gateway and DNS Address settings The updated TCP...

Page 21: ...and alarms that have been previously cleared are not highlighted Once the cause of the alarm has been corrected the alarm is cleared and the unit resumes normal operation If the alarm requires a manual reset click the Reset Alarms button to clear the alarm Test and Balance During startup commissioning or troubleshooting of the unit it may be necessary to force the controller into a certain operati...

Page 22: ...e Mode is intended to be used for short time intervals for a startup or test balance procedures If the unit has been in a Force Mode for longer than 30 minutes without any changes being made to any of the Force Mode settings the unit returns to normal operation If it is determined that economizer minimum positions or blower speed settings need to be adjusted to meet airflow requirements for the si...

Page 23: ...ters Import Export select Export from the dropdown menu select the preferred Memory Type enter a value for the Export File Name and click on the Confirm toggle switch Selecting Internal Flash Memory as the Memory Type will save the file to the controller s internal memory Selecting USB will save the file to a connected USB device The export file can be copied from the controller s internal flash m...

Page 24: ...DAIKIN ILINQ QUICK START GUIDE 24 ...

Page 25: ...ensor Required Yes No Measured Value Controller Value Space CO2 Sensor Offset Entered Comments Configure Date Time Controller Time Controller Timezone Comments Configure Time Schedule Comments Verify Unit Configuration Comments Modify TCP IP Settings Per Site Requirements DHCP Enabled Disabled IP Address Subnet Mask Default Gateway DNS Comments Modify BACnet Settings Per Site Requirements BACnet C...

Page 26: ...th relevant local and national regulations and with the instructions in this installation manual Improper installation may cause electric shock or fire Only use specified accessories and parts for installation Failure to use specified parts may result in electric shock fire or controller damage Do not disassemble reconstruct or repair Electric shock or fire may occur Only use specified wiring and ...

Reviews: