FXZQ20~50M8V1B
VRV System air conditioners
4PW25085-1C

Installation and operation manual

5

2.

After piping work is finished, check if drainage flows
smoothly.

Open the water inlet lid, add approximately 2 l of water
gradually and check the drainage flow.

Method of adding water. See 

figure 13

.

When electric wiring work is finished

Check drainage flow during COOL running, explained in the chapter

"Test operation" on page 8

.

When electric wiring work is not finished

Remove the switch box lid and connect the power supply and
remote controller to the terminals.

See 

figure 22

.

Next, press the inspection/test operation button 

 on the

remote controller. The unit will engage the test operation
mode. Press the operation mode selector button 

 until

selecting fan operation 

. Then, press the on/off button

. The indoor unit fan and drain pump will start up. Check

that the water has drained from the unit. Press 

 to go

back to the first mode.

Note that the fan also starts rotating.

Attach the switch box lid as before.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.

Be sure to ground the air conditioner.

Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.

Gas pipes: might cause explosions or fire if gas leaks.

Water pipes: no grounding effect if hard vinyl piping is used. 

Telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during lightning
storms.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

1

Drain pipe

2

Service drain outlet with rubber plug. Use this outlet to drain 
water from the drain pan.

3

Plastic container for pouring

Drain piping connections
Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.

Keep in mind that it will become the cause of getting
drain pipe blocked if water collects on drain pipe.

1

Switch box lid

2

Remove the switch box lid (take off 2 screws)

3

Power supply terminal block

4

Remote controller terminal block

5

Remote controller wiring

TEST

TEST

Units

Power 

supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

FXZQ20

50

220-240

264

198

0.8

15

0.055

0.6

FXZQ25

0.8

15

0.055

0.6

FXZQ32

0.8

15

0.055

0.6

FXZQ40

0.8

15

0.055

0.6

FXZQ50

0.9

15

0.055

0.7

NOTE

For details, refer to "Electrical data".

Power supply wiring

Remote controller wiring

and Transmission  wiring

Model

Field 

fuses

Wire

Size, 

length

Wire

Size

FXZQ20

15 A

H05VV-U3G 

Wire size 

and length 

must 

comply with 

local 

codes.

Sheathed 

wire 

(2 wire)

0.75~1.25 mm

2

FXZQ25

FXZQ32

FXZQ40

FXZQ50

NOTE

For details, refer to the chapter 

"Wiring example"

on page 7

.

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: 

1000 m 

(total wiring length: 2000 m)

Indoor unit - remote controller: 

500 m

Summary of Contents for FXZQ20M8V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1B System air conditioners ...

Page 2: ... 4 50 100 2 2 3 4 5 1 1 2 45 45 5 6 533 3 575 2 585 660 1 700 4 700 2 585 660 3 575 4 533 1 585 660 8 7 20 20 180 2 1500 1500 1500 2500 1500 1500 1500 1500 1 2 2 1 2 3 3 2 1 4 2 3 4 1 2 1 2 2 1 295 5 4 2 1 3 6 16 1 2 3 4 5 6 7 8 9 10 10 11 11 1 2 3 4 5 6 7 8 9 10 11 1x 1x 1x 8x 4x 1x 1x 1x 1x 2x 1x 2 3 1 4 5 6 7 8 10 9 11 12 15 14 13 17 16 ...

Page 3: ... LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 SETTING 2 1 4 3 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 13 1 2 3 8 7 4 4 5 5 5 6 6 6 5 21 3 2 1 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1 P2 LN P1 P2 F1 F2 T1 T2 L N 6 3 4 2 5 1 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 20 18 19 22 20 21 ...

Page 4: ...ych pod warunkiem że używane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või t...

Page 5: ...tchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also...

Page 6: ... more than 2 5 m so that the user cannot easily touch 3 Air flow directions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller and to close the air outlet s Refer to the installation manual of the optional blocking pad kit and to the chapter Field setting on...

Page 7: ...e unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 9 5 Remove the paper pattern for installation For new ceilings only REFRIGERANT PIPING WORK Fo...

Page 8: ... and drain hose to insulate How to perform piping See figure 15 Precautions Install the drain raising pipes at a height of less than 545 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit NOTE Not recommended but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may foll...

Page 9: ...ion manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding ef...

Page 10: ... branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding terminal Looseness in the connection may deteriorate the protection 4 Remote controller cords and wires connecting the units should be located at least 50 mm away from power supply wiring Not following this guideline may...

Page 11: ...nsorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display indications Display Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by...

Page 12: ...efer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Read the chapter Test operation on page 8 before making a test run without attaching the decoration panel Refer to the installation manual delivered with the decoration panel After installing the decoration panel ensure that there is no space between the unit body and decoration panel Otherw...

Page 13: ...TO CLEAN AIR FILTER display disappears For details refer to the operation manual of the outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove stains use water or neutral detergent When the blade is extremely contaminated remove it as below and clean it How to clean the suction grill 1 Open the suction grill Push both knobs simultaneously...

Page 14: ...ED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR ADAPTOR FOR WIRING X18A CONNECTOR ADAPTOR FOR ELECTRICAL APPENDICES FIELD WIRING BLK BLACK PNK PINK TERMINAL BLU BLUE RED RED CONNECTOR GRN GRE...

Page 15: ...25 27 29 28 26 T1 T2 10 15 mm A D 1 2 3 4 5 6 7 8 15 11 9 15 10 15 8 15 10 15 B 11 12 12 13 14 1 0 1 5 m m C E REMOTE CONTROL TRANSMISSION WIRING FORCED OFF L N L N 25 26 27 28 29 ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25085 1C ...

Reviews: