Installation and operation manual

6

FXZQ20~50M8V1B

VRV System air conditioners

4PW25085-1C

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 25)

Power supply wiring and ground wire
Remove the switch box lid and connect wires of matching
number to the power supply terminal block (3P) inside. (See E).
And connect the ground wire to the terminal block. In doing this,
pull the wires inside through the hole and fix the wires securely
with a field supplied clamp. (See B).
Give enough slack to the wires between the clamp and power
supply terminal block.

Transmission wiring and remote controller wiring.
Remove the switch box lid and pull the wires inside through the
hole and connect to the terminal block for remote controller (6P).
(See C and A). (No polarity) Securely fix the remote controller
cord with a field supplied clamp.
Give enough slack to the wires between the clamp and the
terminal block for the remote controller.

After connection, attach sealing material. (See D).

Be sure to attach it to prevent the infiltration of water from the
outside. (See D).

Precautions 

1

Observe the notes mentioned below when wiring to the power
supply board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. (tightening torque 1.31 N•m±10%)

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

A

Remote controller and transmission wiring

B

Power supply wiring

C

How to connect power supply terminal block (6P) for remote 
controller and transmission wiring

D

Be sure to attach delivered sealing material to prevent the 
infiltration of water as well as any insects and other small 
creatures from the outside. Otherwise a short-circuit may 
occur inside the switch box.

E

How to connect terminal block with ground wire (3P)

1

Switch box lid

2

Wiring diagram label (on the backside of the switch box lid)

3

Remote controller wiring

4

Transmission wiring

5

Terminal block for remote controller (6P)

6

Power supply wiring

7

Power supply terminal block

8

Clamp (field supply)

9

Clamp (field supply)

10

Clamp material

11

Sealing material (supplied with the unit)

12

Wiring to outside

13

Outside

14

Inside

15

Be sure to clamp the wire sheath.
After securing the clamp to the clamp material, cut off any 
extra material.

Summary of Contents for FXZQ20M8V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1B System air conditioners ...

Page 2: ... 4 50 100 2 2 3 4 5 1 1 2 45 45 5 6 533 3 575 2 585 660 1 700 4 700 2 585 660 3 575 4 533 1 585 660 8 7 20 20 180 2 1500 1500 1500 2500 1500 1500 1500 1500 1 2 2 1 2 3 3 2 1 4 2 3 4 1 2 1 2 2 1 295 5 4 2 1 3 6 16 1 2 3 4 5 6 7 8 9 10 10 11 11 1 2 3 4 5 6 7 8 9 10 11 1x 1x 1x 8x 4x 1x 1x 1x 1x 2x 1x 2 3 1 4 5 6 7 8 10 9 11 12 15 14 13 17 16 ...

Page 3: ... LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 SETTING 2 1 4 3 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 13 1 2 3 8 7 4 4 5 5 5 6 6 6 5 21 3 2 1 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1 P2 LN P1 P2 F1 F2 T1 T2 L N 6 3 4 2 5 1 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 20 18 19 22 20 21 ...

Page 4: ...ych pod warunkiem że używane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või t...

Page 5: ...tchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also...

Page 6: ... more than 2 5 m so that the user cannot easily touch 3 Air flow directions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller and to close the air outlet s Refer to the installation manual of the optional blocking pad kit and to the chapter Field setting on...

Page 7: ...e unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 9 5 Remove the paper pattern for installation For new ceilings only REFRIGERANT PIPING WORK Fo...

Page 8: ... and drain hose to insulate How to perform piping See figure 15 Precautions Install the drain raising pipes at a height of less than 545 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit NOTE Not recommended but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may foll...

Page 9: ...ion manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding ef...

Page 10: ... branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding terminal Looseness in the connection may deteriorate the protection 4 Remote controller cords and wires connecting the units should be located at least 50 mm away from power supply wiring Not following this guideline may...

Page 11: ...nsorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display indications Display Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by...

Page 12: ...efer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Read the chapter Test operation on page 8 before making a test run without attaching the decoration panel Refer to the installation manual delivered with the decoration panel After installing the decoration panel ensure that there is no space between the unit body and decoration panel Otherw...

Page 13: ...TO CLEAN AIR FILTER display disappears For details refer to the operation manual of the outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove stains use water or neutral detergent When the blade is extremely contaminated remove it as below and clean it How to clean the suction grill 1 Open the suction grill Push both knobs simultaneously...

Page 14: ...ED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR ADAPTOR FOR WIRING X18A CONNECTOR ADAPTOR FOR ELECTRICAL APPENDICES FIELD WIRING BLK BLACK PNK PINK TERMINAL BLU BLUE RED RED CONNECTOR GRN GRE...

Page 15: ...25 27 29 28 26 T1 T2 10 15 mm A D 1 2 3 4 5 6 7 8 15 11 9 15 10 15 8 15 10 15 B 11 12 12 13 14 1 0 1 5 m m C E REMOTE CONTROL TRANSMISSION WIRING FORCED OFF L N L N 25 26 27 28 29 ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25085 1C ...

Reviews: