Optional accessories

 

„

There are two types of remote controllers: wired and wireless. 
Select a remote controller according to customer’s request and 
install in an appropriate place. 
Refer to catalogues and technical literature for selecting a suitable 
remote controller.

 

„

This indoor unit always requires the optional decoration panel for 
installation. 
Depending on the panel, a separately-sold relay harness adapter 
may be necessary. For details, contact your Daikin dealer.

For the following items, take special care during 

construction and check after installation is finished

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the air tight test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 

name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

There may be danger of electric shock.

Is the wiring sized according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 

outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 

noted down?

The refrigerant charge in the system might not be clear.

Notes to the installer

 

„

Read this manual carefully to ensure correct installation. Be sure to 
instruct the customer how to properly operate the system and show 
him/her the enclosed operation manual.

Selecting installation site

When the conditions in the ceiling are exceeding 86°F (30°C) and a 

relative humidity of 80%, or when fresh air is inducted into the ceiling, 
an additional insulation is required (minimum 3/8 in. (10 mm) 
thickness, polyethylene foam).

For this unit you can select different airflow directions. It is necessary 

to purchase an optional sealing member of air discharge outlet to 
discharge the air in 2 or 3 (closed corners) directions.
Install the unit so that air vents, lights, or machines near the unit do not 

interfere with the airflow.

≥60 (≥1500)

≥80 (≥2000)

≥160 (≥4000)

(A)

≥60 (≥1500)

(B)

≥60 (≥1500)

a

c

b

a

Unit: in. (mm)

Indoor unit

Lighting 

The figure describes a surface mounted light, but a recessed 

ceiling light is not restricted.

Air fan

If the air outlet is closed, space marked (A) should be 8 in.  

(200 mm) at least.

≥60 in. (≥1500 mm) from any static obstruction

Select an installation site where the following conditions are fulfilled 

and that meets your customer’s approval.
•  Where optimum air distribution can be ensured.
•  Where nothing blocks air passage.
•  Where condensate water can be properly drained.
•  Where the false ceiling is not noticeably on an incline.
• 

Where sufficient clearance for maintenance and service can be 

ensured.

• 

Where there is no risk of flammable gas leaking.

• 

The equipment is not intended for use in a potentially explosive 

atmosphere.

•  Where piping between indoor and outdoor units is possible within the 

allowable limit. (Refer to the installation manual of the outdoor unit.)

•  Keep indoor unit, outdoor unit, transmission wiring and remote 

controller wiring at least 3.5 ft. (1 m) away from televisions and 

radios. This is to prevent image interference and noise in those 
electrical appliances. (Noise may be generated depending on the 
conditions under which the electric wave is generated, even if 

3.5 ft. (1 m) is kept.)

•  When installing the wireless remote controller kit, the 

communication distance between wireless remote controller and 

indoor unit might be reduced if there are fluorescent lights 

(inverter or rapid start types) in the room. The indoor unit must be 

installed as far as possible away from fluorescent lights.

Ceiling height
This indoor unit may be installed on ceilings up to 11-1/2 ft. (3.5 m) 

in height. However, it becomes necessary to make field settings 

using the remote controller when installing the unit at a height over 
8-3/4 ft. (2.7 m).
To avoid accidental touching, it is recommended to install the unit 
higher than 8-1/4 ft. (2.5 m).
Refer to “Field setting” on page 8 and to the decoration panel 
installation manual.

Airflow directions
Select the airflow directions best suited to the room and point of 

installation. (For air discharge in 3 directions, it is necessary to 

make field settings by means of the remote controller and to close 

the air outlet(s). Refer to the installation manual of the optional 
sealing member of air discharge outlet and to “Field setting” on 

page 8. (See figure 1) 

Air discharge in 4 directions

Air discharge in 3 directions

Air discharge in 2 directions

01_EN_3P493125-3C.indd   2

2021/12/09   11:43:29

Summary of Contents for FXZQ05TBVJU

Page 1: ... manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este manual debe permanecer con el propi...

Page 2: ...60B3 8 1 16 205 25 3 8 645 H1 H2 8 11 16 220 24 13 16 630 1 9 10 5 6 5 2 7 4 3 5 6 7 7 1 16 180 13 16 20 13 16 20 2 1 2 63 27 9 16 700 1 22 5 8 575 3 21 533 4 23 1 16 26 585 660 2 23 1 16 26 585 660 2 27 9 16 700 1 23 1 16 26 585 660 2 22 5 8 575 3 21 533 4 8 11 1 4 285 6 24 7 16 620 1 7 1 2 190 23 1 16 23 7 16 585 595 2 22 5 8 575 3 24 7 16 620 1 23 1 16 23 7 16 585 595 2 1 2 12 5 1 2 12 5 22 5 8...

Page 3: ...2 3 5 IN D OUT D F1 F2 F1 F2 Control box L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 L2 L1 L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 L1 L2 1 4 2 3 14 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1 P2 L2 L1 P1 P2 F1 F2 T1 T2 1 6 2 3 10 Unit in mm 2 1 5 4 4 100 3 11 2 2 L1 L2 L1 L2 1 L1 L2 L1 L2 L1 L2 00_CV_3P493125 3C indd 3 2022 02 07 14 32 30 ...

Page 4: ...l must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant leaks in the event of an accident in a closed ambient space can ...

Page 5: ...g for indoor models that can be connected Normal operation is not possible when connected to other units Handheld remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor u...

Page 6: ...e connectable outdoor units must be designed exclusively for R410A Precautions This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to en...

Page 7: ... 1500 B 60 1500 a c b a Unit in mm a Indoor unit b Lighting The figure describes a surface mounted light but a recessed ceiling light is not restricted c Air fan A If the air outlet is closed space marked A should be 8 in 200 mm at least B 60 in 1500 mm from any static obstruction 1 Select an installation site where the following conditions are fulfilled and that meets your customer s approval Whe...

Page 8: ...ing in the ceiling it may be necessary to reinforce ceiling beams to keep the ceiling level and to prevent it from vibrating Consult the builder for details 3 Install the suspension bolts Use either a M8 M10 size bolt or equivalent Use anchors for existing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight...

Page 9: ... annealed material for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque Overtightening may damage the flare and cause leaks Table 1 Piping size in mm Tightening torque lbf ft N m Flare dimensions A in mm Flare in mm f1 4 6 4 10 4 12 7 15 7 1 5 0 342 0 358 8 9 0 2 R0 016 0 031 0 4 0 8 f1 2 12 7 36 5 44 5 54 9 5 4 0 638 0 654 16 4 0 2 Re...

Page 10: ...is finished attach the drain sealing pad 4 supplied with the unit over the uncovered part of the drain socket between drain hose and unit body 1 5 2 3 4 3 4 2 A A A A 1 1 Drain socket attached to the unit 2 Drain hose supplied with the unit 3 Metal clamp supplied with the unit NOTE Bend the tip of the metal clamp to avoid tearing the sealing 4 Large sealing pad supplied with the unit 5 Drain pipin...

Page 11: ...ctrician and must comply with relevant national state and local code Use copper wire only Follow the Wiring diagram label attached to the back side of the control box cover to wire outdoor unit indoor units and the remote controller For details on hooking up the remote controller refer to the installation manual of the remote controller All wiring must be performed by an authorized electrician A m...

Page 12: ...connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When clamping wiring use the clamps supplied with the unit to prevent outside force being exerted on the wiring connections Tie up firmly When doing the wiring make sure the wiring is neat and does not cause the control box to stick up Close the cover firmly When connecting wires of...

Page 13: ...l supplied with the decoration panel After installing the decoration panel ensure that there is no space between the unit body and decoration panel Otherwise air may leak through the gap and cause condensation Field setting Field setting must be made from the remote controller in accordance with the installation condition Setting can be made by changing the Mode No First code No and Second code No...

Page 14: ...for group connection 10 6 01 has priority and for individual connection 10 2 01 10 2 02 or 10 2 03 have priority Note 6 More settings for Differential automatic changeover temperature are Second code No 05 7 2 F 4 C 06 9 0 F 5 C 07 10 8 F 6 C 08 12 6 F 7 C When using wireless remote controllers it is necessary to use address setting Refer to the installation manual attached to the wireless remote ...

Page 15: ...utdoor unit NOTE When performing field settings or test operation always attach the decoration panel Otherwise this may cause condensation The operation lamp of the remote controller will flash when an error occurs Check the error code on the display to identify the trouble Refer to the installation manual attached to the outdoor unit or contact your dealer Check the operation of the horizontal bl...

Page 16: ... 2204 HT 3P493125 3C EM21A014 Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 3C indd 4 2022 02 07 14 32 30 ...

Reviews: