Outline of Control (Outdoor Unit)
SiE 00-07
58
Function R-407C PLUS Series
3.11
Low Pressure Protection Control
The following control is provided to protect the compressors from abnormal decrease of low pressure (LP).
Normal operation
Normal operation
E4 malfunction
stop
Forced thermostat
OFF
LP<0.15MPa
LP<0.05MPa
LP>0.10MPa
LP<0.03MPa
LP<0.0MPa
Compressor
operation
frequency
31Hz+OFF+OFF
LP<0.05MPa
SVP (for hot gas
bypass) : ON
LP<0.08MPa
SVP (for hot gas
bypass) : OFF
SVP (for hot gas
bypass) : ON
OR
·&
·
Tes>
Ta
-5
·LP
>0.20MPa
·30 sec elapse
OR
·&
·&
·LP
>0.13MPa
·
Ta>5˚C
·
LP<0.098MPa
·
Ta
≤
5˚C
OR
·&
·&
·LP
<0.08MPa
·
Ta>5˚C
·
LP<0.049MPa
·
Ta
≤
5˚C
∗
Malfunction reset
LP>0.09MPa
LP>0.10MPa
(Monitoring LP every 30 sec.)
LP>0.07MPa
(Monitoring LP every 1 min)
Ta : Outdoor air temp. (˚C)
Tes : Low pressure equivalent
saturation temp. (˚C)
[Heating mode]
[Cooling mode]
SVP (for hot
gas bypass) : ON
LP > 0.13 MPa
Upper limit frequency =
Maximum frequency
1-step increase for
compressor
operation frequency
[Oil return mode (common for cooling / heating)]
Restriction for upper
limit compressor
operation frequency
∗
1
(V0822)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...