SiE 00-07
Troubleshooting (OP: Schedule Timer)
Troubleshooting R-407C PLUS Series
173
7.4
Improper Combination of Optional Controllers for Centralized Control
Remote Controller
Display
MA
Supposed Causes
Improper combination of optional controllers for centralized control
More than one master controller is connected.
Defect of PC board of optional controller for centralized control
Troubleshooting
Disconnect the schedule timer's
individual / combined connector
and reset the power supply for all
optional controllers for centralized
control simultaneously.
Arrange so that the connector for
setting master control is connected
to one controller for centralized
control and reset the power supply
for all optional controllers for
centralized control simultaneously.
Disconnect the connector for
setting master control from the
master controller, connect to
another optional controller for
centralized control and
simultaneously reset all optional
controllers for centralized control
again. The controller connected by
the connector for setting master
control when the malfunction is
cleared is defective and must be
replaced.
Reset the power supply for all
optional controllers for
centralized control
simultaneously.
YES
YES
NO
Is the schedule
timer connected?
Are
there two or
more optional controllers
for centralized control connected
with the connector for
setting master
control?
YES
Is the schedule
timer's individual/combined
connector connected?
NO
NO
Cannot be used in combination
with a wiring adaptor for electrical
appendices. Remove the wiring
adaptor for electrical appendices
and reset the power supply for all
optional controllers for centralized
control simultaneously.
YES
Is the wiring
adaptor for electrical
appendices connected?
NO
Schedule timer and data station
cannot be used in combination.
Disconnect either the schedule
timer or data station and reset the
power supply for all optional
controllers for centralized control
simultaneously.
YES
Is a data station connected?
NO
Schedule timer and parallel
interface cannot be used in
combination. Disconnect either the
schedule timer or parallel interface
and reset the power supply for all
optional controllers for centralized
control simultaneously.
YES
Is a parallel interface
connected?
NO
If the malfunction is still not cleared:
(VF077)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...