1.14
Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn on/off by central remote controller only.
(Cannot be turned on/off by remote controller.)
OFF control only possible by remote controller
Used when you want to turn on by central remote controller only, and off by remote controller only.
Centralized
Used when you want to turn on by central remote controller only, and turn on/off freely by remote
controller during set time.
Individual
Used when you want to turn on/off by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want to start
operation by central remote controller when time of system start is programmed.
How to Select
Operation Mode
Whether operation by remote controller will be possible or not for turning on/off, controlling temperature or
setting operation mode is selected and decided by the operation mode given on the right edge of the table
below.
Do not select “timer operation possible by remote controller” if not using a remote controller. Operation by
timer is impossible in this case.
∗
1. Factory setting
ON by remote
controller
(Unified ON by
central remote
controller)
OFF by remote
controller
(Unified OFF by
central remote
controller)
Temperature
control by
remote controller
Operation mode
setting by
remote controller
OFF by
remote
controller
Control
mode is "1."
Example
↓
Rejection
↓
Rejection
↓
Rejection
↓
Acceptance
↓
Acceptance
(VL069)
Control mode
Control by remote controller
Control
mode
Operation
OFF
Temperature
control
Operation
mode
setting
Unified operation, individual
operation by central remote
controller, or operation
controlled by timer
Unified OFF, individual stop
by central remote controller,
or timer stop
ON/OFF control
impossible by
remote controller
Rejection (Example)
Rejection (Example)
Rejection
(Example)
Rejection
Acceptance
0
Rejection
10
Acceptance
(Example)
Acceptance
(Example)
1(Example)
Rejection
11
OFF control only
possible by remote
controller
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance
Acceptance
3
Rejection
13
Centralized
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance
Acceptance
5
Rejection
15
Individual
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance
Acceptance
7
∗
1
Rejection
17
Timer operation
possible by remote
controller
Acceptance
(During timer at ON position
only)
Acceptance
(During timer at ON position
only)
Rejection
Acceptance
8
Rejection
18
Acceptance
Acceptance
9
Rejection
19
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...