Capacity Tables
EDUS391437-F15
10
FXUQ-PVJU
8. Capacity Tables
8.1
Cooling Capacity at Te: 43°F (6°C)
TC:
Total capacity: MBH
SHC: Sensible heat capacity: MBH
Notes:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies the required heat load.
2.
shows rated condition.
8.2
Heating Capacity
TC:
Total capacity: MBH
Notes:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies the required heat load.
2.
shows rated condition.
8.3
Correction Factor for Cooling Capacity at Te: 48°F (9°C)
TC:
Total capacity
SHF: Sensible heat factor
Model
Capacity
indication
Indoor air temp. °FWB (Te: 43°F (6°C))
61
64
67
70
72
75
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
FXUQ18PVJU
18
14.2 11.8 16.1 12.9 18.0 13.7 18.4 13.6 18.6 13.0 18.9 12.8
FXUQ24PVJU
24
19.0 15.4 21.5 16.9 24.0 18.0 24.5 17.8 24.8 17.0 25.3 16.6
FXUQ30PVJU
30
23.7 18.8 26.8 20.7 30.0 22.1 30.6 21.8 31.0 20.9 31.6 20.2
FXUQ36PVJU
36
28.4 22.1 32.2 24.2 36.0 26.0 36.7 25.7 37.2 24.7 37.9 23.6
Model
Capacity
indication
Indoor air temp. °FDB
62
65
68
70
72
75
TC
TC
TC
TC
TC
TC
MBH
MBH
MBH
MBH
MBH
MBH
FXUQ18PVJU
18
23.3 21.9 20.7 20.0 19.3 18.1
FXUQ24PVJU
24
31.5 29.5 28.0 27.0 26.0 24.5
FXUQ30PVJU
30
39.7 37.1 35.3 34.0 32.7 30.9
FXUQ36PVJU
36
46.7 43.7 41.5 40.0 38.5 36.3
Model
Capacity
indication
Indoor air temp. °FWB (Te: 48°F (9°C))
61
64
67
70
72
75
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
FXUQ18PVJU
18
0.706
1.162
0.765
1.108
0.786
1.090
0.806
1.073
0.841
1.045
0.865
1.028
FXUQ24PVJU
24
0.706
1.162
0.765
1.108
0.786
1.090
0.806
1.073
0.841
1.045
0.865
1.028
FXUQ30PVJU
30
0.707
1.161
0.773
1.103
0.795
1.087
0.811
1.077
0.842
1.053
0.865
1.035
FXUQ36PVJU
36
0.707
1.161
0.773
1.103
0.795
1.087
0.811
1.077
0.842
1.053
0.865
1.035
Refer to the correction factor table below when a
residential indoor unit is connected to your
VRV
system.
Summary of Contents for FXUQ PVJU Series
Page 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Page 2: ......
Page 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Page 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Page 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Page 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Page 42: ......
Page 43: ......