• Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
1
Specifications
1-3 Electrical Specifications (60Hz)
FXSQ20MVE9
FXSQ25MVE9
FXSQ32MVE9
FXSQ40MVE9
FXSQ50MVE9
FXSQ63MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
0.6
0.6
0.8
0.9
1.0
1.4
Maximum fuse amps (MFA)
A
15
15
15
15
15
15
Full load amps (FLA)
A
0.5
0.5
0.6
0.7
0.8
1.1
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 Electrical Specifications (60Hz)
FXSQ80MVE9
FXSQ100MVE9
FXSQ125MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
1.8
1.9
2.5
Maximum fuse amps (MFA)
A
15
15
15
Full load amps (FLA)
A
1.4
1.5
2.0
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker