background image

English

4

b. Items to be checked at time of delivery

Also review the “SAFETY CONSIDERATIONS”

c. Points for explanation about operations

2-4

NOTE TO INSTALLER

• Be sure to instruct customers how to properly operate the 

unit (especially cleaning filters, operating different functions, 
and adjusting the temperature) by having them carry out 
operations themselves while looking at the manual.

3.

SELECTING INSTALLATION SITE

Please attach additional thermal insulation material to the unit 
body when it is believed that the relative humidity in the ceiling 
exceeds 80%. Use glass wool, polyethylene foam, or similar with 
a thickness of 3/8in. or more as thermal insulation material.

(1) Select an installation site where the following conditions are 

fulfilled and that meets with your customer’s approval.
• In the upper space (including the back of the ceiling) of the 

indoor unit where there is no possible dripping of water 
from the refrigerant pipe, drain pipe, water pipe, etc.

• Where optimum air distribution can be ensured.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• If supporting structural members are not strong enough 

to take the unit’s weight, the unit could fall out of place 
abd cause serious injury.

• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service 

can be ensured. 

(Refer to Fig. 1)

• Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation 
manual of the outdoor unit.)

CAUTION

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 3.3ft. away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3ft. may not 
be sufficient enough to eliminate the noise.)

(2) Use suspension bolts for installation. Check whether 

the ceiling is strong enough to support the weight of 
the unit or not. If there is a risk, reinforce the ceiling 
before installing the unit.

4.

PREPARATIONS BEFORE INSTALLATION

(1) Relative positions of indoor unit and suspension bolt. 

(Refer to Fig. 2)

(2) Install a canvass duct to the air discharge outlet and air inlet 

so that vibration from the machine body isn’t transmitted to 
the duct or ceiling.
You should also apply acoustic (insulation material) to the 
inside of the duct, and vibration insulation rubber to the sus-
pension bolts.

(3) Install suspension bolts.

(Use bolts of 3/8in. diameter.)
• Install the equipment where supporting structures are 

strong enough to bear the equipment’s weight. Use 
embedded inserts or anchor bolts with new buildings and 
hole-in-anchors with old buildings.

Items to be checked

Check

Did you explain about operations while showing the instruction 
manual to your customer?

Did you hand the instruction manual over to your customer?

The items with 

WARNING and 

CAUTION marks in the instruc-

tion manual are the items pertaining to possibilities for bodily injury 
and material damage in addition to the general usage of the product. 
Accordingly, it is necessary that you make a full explanation about 
the described contents and also ask your customers to read the 
instruction manual.

Fig. 1

Min. 25-9/16

(service space)

18-1/2

(length: in.)

Fig. 2

Indoor unit

Air outlet

Inspection hatch  
23-5/8

51

Air inlet

Approx. 

5-7/8 

43-5/16

43-5/16 or more

45-3/16

54-5/16

(service space)

Suspension 
bolt (× 4)

(length: in.)

25-9/16 or more

(service space)

Anchor

Indoor unit

Long nut or turn-buckle

Installation example

Note)   All the above parts are field supplied. 

Suspension bolt

Ceiling slab

01_EN_3P086156-13Y.fm  Page 4  Wednesday, September 16, 2009  2:22 PM

Summary of Contents for FXMQ72MVJU

Page 1: ...LATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE...

Page 2: ...installation work check that the re frigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause se r...

Page 3: ...R 410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work prope...

Page 4: ...ling the indoor unit Entrust installation to the place of purchase or a qualified ser viceman Improper installation could lead to leaks and in worse cases electric shock of fire Use only parts provide...

Page 5: ...rference or noise Depending on the radio waves a distance of 3 3ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether the ceiling is strong enoug...

Page 6: ...not possible if the types of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil inside the flare portions before conne...

Page 7: ...zing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having...

Page 8: ...tiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and a...

Page 9: ...97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged...

Page 10: ...F2 Control box L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1 Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor u...

Page 11: ...Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp o...

Page 12: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0909 HT 3P086156 13Y EM09A017 00_CV_3P086156 13Y fm Page 2 Wednesday September 9 2009 2 52 PM...

Reviews: