Summary of Contents for FXMQ48MFVJU

Page 1: ...Outdoor Air Processing Unit FXMQ MFVJU EDUS39 900B F10 202103 Engineering Data 60 Hz ...

Page 2: ......

Page 3: ...ensions 5 4 Center of Gravity 7 5 Piping Diagrams 8 6 Wiring Diagrams 9 7 Electric Characteristics 11 8 Capacity Tables 12 9 Operation Limit 15 10 Fan Performances 18 11 Sound Levels Reference Data 21 11 1 Overall 21 11 2 Octave Band Level 22 12 Accessories 23 12 1 Optional Accessories for Unit 23 ...

Page 4: ...outdoor air processing unit can be connected to the same refrigerant line enabling enhanced design flexibility Design flexibility with a capacity range up to 96 MBH The nominal airflow rates are 635 988 and 1 236 CFM Improved ductwork and filtration flexibility with ESP capability of up to 1 03 W G Low profile design of less than 19 high to reduce required installation space Indoor Air Quality opt...

Page 5: ...tor for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve H5 Connectable outdoor units R410A VRV series R410A VRV series Standard accessories Operation manual Installation manual Sealing pads Screws Clamps Operation manual Installation manual Sealing pads Screws Clamps Connection pipes Note 1 Nominal cooling capacities are base...

Page 6: ...able outdoor units R410A VRV series Standard accessories Operation manual Installation manual Sealing pads Screws Clamps Connection pipes Note 1 Nominal cooling capacities are based on the following conditions Outdoor temperature 91 FDB 82 FWB 68 RH Discharge set temperature 64 FDB Equivalent refrigerant piping length 25 ft horizontal 2 Nominal heating capacities are based on the following conditi...

Page 7: ...5 FXMQ MFVJU EDUS39 900B F10 3 Dimensions FXMQ48MFVJU 3D065452A Unit in ...

Page 8: ...6 FXMQ MFVJU EDUS39 900B F10 FXMQ72 96MFVJU 3D065453A Unit in ...

Page 9: ...r of Gravity FXMQ48 96MFVJU Unit in 4D065444 Model FXMQ48MFVJU FXMQ72MFVJU FXMQ96MFVJU Product Mass 190Lbs 271Lbs 271Lbs AA 30 11 16 54 5 16 54 9 16 AB 27 3 8 51 51 AC 23 5 8 22 7 16 22 7 16 AD 9 13 16 9 13 16 9 13 16 AE 13 23 5 8 23 5 8 ...

Page 10: ...8 FXMQ MFVJU EDUS39 900B F10 5 Piping Diagrams FXMQ48 96MFVJU Unit in Model Gas Liquid FXMQ48MFVJU ɸ5 8 ɸ3 8 FXMQ72MFVJU ɸ3 4 FXMQ96MFVJU ɸ7 8 4D018650D ...

Page 11: ...CCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 3 IN CASE CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INSTALLATION MANUAL ATTACHED TO THE UNIT 4 DO NOT REMOVE SHORT CIRCUIT CONNECTOR OF X9A 5 SYMBOLS SHOW AS FOLLOWS RED RED BLK BLACK WHT WHITE YLW YELLOW PPL PURPLE GRY GRAY BLU BLUE PNK PINK ORG ORANGE G...

Page 12: ...NETIC RELAY M1P KSR MAGNETIC RELAY Y1S M1F MOTOR FAN Q1M THERMAL PROTECTOR M1F EMBEDDED 135 C R1T THERMISTOR SUCTION AIR R2T THERMISTOR COIL LIQUID R3T THERMISTOR COIL GAS R4T THERMISTOR DISCHARGE AIR T1R TRANSFORMAR 208 V 230 V 25 VA X1M TERMINAL BLOCK POWER X2M TERMINAL BLOCK CONTROL X3M TERMINAL BLOCK X51A X52A CONNECTOR Y1E ELECTRIC EXPANSION VALVE Y1S SOLENOID VALVE HOT GAS CONNECTOR FOR OPTI...

Page 13: ... 0 380 3 3 638 638 Symbol MCA Min Circuit Amps A MOP Max Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Amps A IFM Indoor Fan Motor SCCR Short Circuit Current Rating Note 1 Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits 2 Maximum allowable voltage unbalance between phase i...

Page 14: ...or air temperature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 32600 32600 32 30000 37 26600 26600 26600 42 21500 21500 21500 52 16800 16800 16800 57 12100 12100 12100 Note 1 The above capacities are based on the following conditions Air discharge temperature setting 64 F for cooling operation 77 F for heating factory setting Equivalent piping length 25 ft Le...

Page 15: ...mperature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 50700 50700 32 47000 37 41200 41200 41200 42 33800 33800 33800 52 26300 26300 26300 57 18900 18900 18900 Note 1 The above capacities are based on the following conditions Air discharge temperature setting 64 F for cooling operation 77 F for heating factory setting Equivalent piping length 25 ft Level diffe...

Page 16: ...temperature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 63700 63700 32 59000 37 51800 51800 51800 42 42300 42300 42300 52 33200 33200 33200 57 23700 23700 23700 Note 1 The above capacities are based on the following conditions Air discharge temperature setting 64 F for cooling operation 77 F for heating factory setting Equivalent piping length 25 ft Level dif...

Page 17: ...may not match the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equivalent pipe length 25 ft Level difference 0 ft 3 The discharge air temperature may not match the temperature setting for too small outdoor air processing capacity 4 The system will not opera...

Page 18: ... the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equivalent pipe length 25 ft Level difference 0 ft 3 The discharge air temperature may not match the temperature setting for too small outdoor air processing capacity 4 The system will not operate in fan mod...

Page 19: ...h the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equivalent pipe length 25 ft Level difference 0 ft 3 The discharge air temperature may not match the temperature setting for too small outdoor air processing capacity 4 The system will not operate in fan mo...

Page 20: ...18 FXMQ MFVJU EDUS39 900B F10 10 Fan Performances FXMQ48MFVJU 3D065649B ...

Page 21: ...19 FXMQ MFVJU EDUS39 900B F10 FXMQ72MFVJU 3D065650B ...

Page 22: ...20 FXMQ MFVJU EDUS39 900B F10 FXMQ96MFVJU 3D065651B ...

Page 23: ...ference Data 11 1 Overall n Location of microphone 6 6 ft 4 9 ft DUCT DISCHARGE SUCTION MICROPHONE DUCT 3 3 ft Note 1 Operation noise differs with operation and ambient conditions dBA Model 208 230 V 60 Hz FXMQ48MFVJU 43 FXMQ72MFVJU 48 FXMQ96MFVJU 48 ...

Page 24: ...22 FXMQ MFVJU EDUS39 900B F10 11 2 Octave Band Level 208 230 V 60 Hz FXMQ48MFVJU FXMQ72MFVJU C 4D068575 C 4D068576 FXMQ96MFVJU C 4D068577 ...

Page 25: ...40 KDJ3705L280 Long life replacement filter KAF371M140 KAF371M280 C 3D065445 Note H1 Filter chamber has a suction type flange Main unit does not have Dimensions and weight of the equipment may vary depending on the options used Some options may not be usable due to the equipment installation conditions so please confirm prior to ordering Some options may not be used in combination Operating sound ...

Page 26: ......

Page 27: ......

Page 28: ... or explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion Read the user s manual carefully before using this product The user ...