• Indoor Unit • FXMQ-P7
2
• VRV Systems • FXMQ-P7
4
2
Specifications
Notes
(1) Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
(2) Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction.
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the value of MCA
Use a circuit breaker instead of a fuse.
Piping connections
Liquid
Type
Flare connection
OD
mm
6.35
9.52
Gas
Type
Flare connection
OD
mm
12.7
15.9
Drain
VP25 (I.D. 25/O.D. 32)
Heat insulation
Both liquid and gas pipes
Drain-up height
mm
625
Safety devices
Item
01
PC board fuse
02
PC board fuse (fan driver)
03
Drain pump fuse
Control systems
Infrared remote control
BRC4C65
Simplified wired remote control for hotel
applications
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
Wired remote control
BRC1D52 / BRC1E52A/B
2-2 Electrical Specifications
FXMQ50P7
FXMQ63P7
FXMQ80P7
FXMQ100P7
FXMQ125P7
Power supply
Name
VE
Phase
1~
Frequency
Hz
50/60
Voltage
V
220-240/220
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Minimum circuit amps (MCA)
A
1.4
1.7
2.3
2.9
Maximum fuse amps (MFA)
A
16
Current - 60Hz
Minimum circuit amps (MCA)
A
1.4
1.7
2.3
2.9
Maximum fuse amps (MFA)
A
16
2-1 Technical Specifications
FXMQ50P7
FXMQ63P7
FXMQ80P7
FXMQ100P7
FXMQ125P7